Mitsubishi Electronics MSZ-ANA, MS-AWA, MUZ-ANA, MUY-ANA, MU-AWA, MSY-ANA, MXZ-ANA manual MXZ-2A, MXZ-3A

Models: MUY-ANA MSY-ANA MS-AWA MUZ-ANA MXZ-ANA MSZ-ANA MU-AWA

1 28
Download 28 pages 7.08 Kb
Page 26
Image 26
(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)

Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.

MXZ-2A

 

 

LEV opening

Discharge temperature (˚F)

correction (pulse)

 

 

COOL

HEAT

More than Target discharge temperature+18

5

8

Target discharge temperature+18

to Target discharge temperature+9

4

3

Target discharge temperature+9

to Target discharge temperature+3.6

2

1

Target discharge temperature+3.6 to Target discharge temperature-3.6

0

0

Target discharge temperature-3.6

to Target discharge temperature-9

-1

-1

Target discharge temperature-9

to Target discharge temperature-18

-3

-2

Target discharge temperature-18 or less

-4

-3

MXZ-3A

 

 

LEV opening

Discharge temperature (˚F)

correction (pulse)

 

 

COOL

HEAT

More than Target discharge temperature+21.6

4

6

Target discharge temperature+21.6

to Target discharge temperature+9

2

2

Target discharge temperature+9

to Target discharge temperature+5.4

1

1

Target discharge temperature+5.4

to Target discharge temperature-5.4

0

0

Target discharge temperature-5.4

to Target discharge temperature-9

-1

-1

Target discharge temperature-9

to Target discharge temperature-21.6

-3

-2

Target discharge temperature-21.6 or less

-8

-8

(2)Separate correction (COOL,DRY) (Correction by the separate super heat)

a)Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all.

1Calculate each super heat of the unit from the expression below;

(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)

2Separate correction is performed according to each super heat in the table below.

MXZ-2A

Superheat

LEV opening

correction (pulse)

 

 

 

more than 16.2

3

10.8 to 16.2

2

5.4 to 10.8

1

5.4 or less

0

MXZ-3A

Superheat

LEV opening

correction (pulse)

 

 

 

more than 16.2

12

10.8 to 16.2

8

5.4 to 10.8

4

5.4 or less

0

26

Page 26
Image 26
Mitsubishi Electronics MSZ-ANA manual Super heat = Each gas pipe temperature - Minimum gas pipe temperature, MXZ-2A, MXZ-3A