1-4. INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation. <Indoor unit>
(1) | Installation plate | 1 |
| Attachment screws for the installa- |
|
(2) | tion plate | 5 |
| 4 × 25 mm |
|
|
|
|
(3) | Remote controller holder | 1 |
|
|
|
| Screws for the remote controller |
|
(4) | holder | 2 |
| 3.5 × 16 mm (Black) |
|
|
|
|
(5) | Battery (AAA) for (6) | 2 |
|
|
|
(6) | Wireless remote controller | 1 |
in.(84 | ||
mm) or | ||
more | ||
|
Use the wall hole sleeve
(C)to prevent indoor/out- door connecting wire (A) from contacting metal parts in the wall and to protect the wiring from rodents.
| Wall hole cover (D) |
Indoor unit | Seal the wall hole |
| gap with putty (H). |
Wall hole | Attach the pipe to |
sleeve (C) | |
| wall with pipe at- |
| tachment strap (E). |
Cut off the | Pipe attachment |
extra length. | strap (E) |
Attachment screw (F)
(7) | Felt tape (For left or | 1 | |
|
|
| |
(8) | 1 | ||
|
|
| |
(9) | 3ODWLQXPGHRGRUL]LQJ¿OWHU | 1 | |
|
|
| |
|
| ||
|
|
| |
(A) | Indoor/outdoor unit connecting wire* | 1 | |
|
|
| |
(B) | Extension pipe | 1 | |
|
|
| |
(C) | Wall hole sleeve | 1 | |
|
|
| |
(D) | Wall hole cover | 1 | |
|
|
| |
(E) | Pipe attachment strap | 2 to 5 | |
|
|
| |
(F) | Screw for (E) 4 × 20 mm | 2 to 5 | |
|
|
| |
(G) | Piping tape | 1 | |
|
|
| |
(H) | Putty | 1 | |
|
|
| |
| Drain hose |
| |
(I) | (or soft PVC hose, 19/32 in. [15 mm] | 2 to 5 | |
inner diameter or hard PVC pipe | |||
|
| ||
| VP16) |
| |
|
|
| |
(J) | Refrigerant oil | 1 | |
|
|
| |
(K) | Power supply cord | 1 | |
|
|
|
* Note:
Place indoor/outdoor unit connecting wire (A) and power supply cord (K) at least 3 ft. (1 m) away from the TV antenna wire.
in.(84 | ||
mm) or | ||
more | ||
|
9/32 in. (7 mm) or more
After the leak test, apply insulating mate- rial tightly so that there is no gap.
When the piping is to be attached to a wall comprised of tin plate or metal netting, use chemically treated wooden piece 25/32 in. (20 mm) or thicker between the wall and the piping, or wrap insulation vinyl tape 7 to 8 turns around the piping.
To use existing piping, perform COOL operation for 30 minutes and pump down before removing the old air conditioner.
5HPDNHÀDUHDFFRUGLQJWRWKHGLPHQVLRQ for new refrigerant.
| 4 |
(100 in. | |
or | mm) |
| more |
| . |
in | |
8 | mm) |
| |
(200more | |
or |
|
Basically open 4 in. (100 mm) or more without any obstruction in front and on both sides of the unit.
4 in.
(100 mm)
or more
(B)
| 14 | in. | |
(350 |
| ||
or |
| mm) | |
| more |
Unit: inch
|
| |
| 5- | |
| 15/16 | Air inlet |
|
| |
|
| |
Air outlet | ||
|
Unit: mm
800 |
500 |
Open two sides of left, right, or rear side.
Units should be installed by licensed contractor according to local code requirements.
|
| 150 |
|
| Air inlet |
344.5 | 285 | |
|
| 40 |
Air outlet |