2. INDOOR UNIT INSTALLATION
2-1. ATTACHING THE INSTALLATION PLATE
•Find a stud in the wall to attach installation plate (1) horizontally on the wall with screws (2).
•To prevent installation plate (1) from vibrating, be sure to install the attachment screws in the holes indicated in the illustration. For added support, additional screws may also be installed in other holes.
•When the indoor unit is to be attached to a concrete wall using recessed bolts, secure installation plate (1) using 7/16 in. x 13/16 in · 7/16 in. x 1 in. (11 mm × 20 mm · 11 mm × 26 mm) oval hole
,IWKHUHFHVVHGEROWLVWRRORQJFKDQJHLWIRUDVKRUWHURQH¿HOGVXSSOLHG
2-2. DRILLING
1)Determine where the holes will be located on the wall.
2)Drill a ø
3)Insert wall hole sleeve (C).
2-3. CONNECTING WIRES FOR INDOOR UNIT
Note:
When the indoor unit is powered from the outdoor unit, depending on local code, a discon- nect switch needs to be installed to a power supply circuit.
1)Remove the panel assembly. (Refer to
2)Place the upper part of the indoor unit on the installation plate.
3)Remove corner box and conduit cover.
4)Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to conduit cover with lock nut. The thread of the installed conduit pipe / elbow joint appear- ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less than
5)Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical parts box.
6)Process the end of indoor/outdoor unit connecting wire (A) (Fig. 3). Attach it to the terminal block. Be careful not to make
7)Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas- tened.
8)Secure indoor/outdoor unit connecting wire (A) and the ground wire with conduit cover. Never fail to hook the claw of the conduit cover to the electrical box. Attach the conduit cover securely. (Fig. 4)
9)According to the piping direction, remove the shaded part of the left side of box (Fig. 5) or corner box (Fig.6). Reinstall corner box and front panel.
Ceiling |
| ||
Bind the line to the center hole. | |||
and left back piping (using spacer) | |||
| |||
Installation plate (1) |
|
| |
Level |
|
| |
| |||
(84 mm) | (84 mm) |
| |
or more | or more |
| |
| 4 in. |
| |
Wall | (100 mm) | Wall |
Attachment screw (2) | Align the plumb | Insert | Align the | Center of |
the | scale with | ø | ||
| line with the | scale. * | ||
| the line. * | (65 mm) hole | ||
| mark . | Plumb |
|
|
|
|
|
|
* Same for left hole.
| Wall |
Ø | |
(65 mm) | |
| |
| Outdoor side |
|
| Lock nut |
|
Fixing |
| Conduit |
|
| cover | Indoor terminal | |
screw |
|
| |
|
| block | |
|
|
| |
Conduit pipe | or | Elbow joint |
|
(for rear piping) |
| (for right, left, or downward piping) |
•Connect wires to the appropriate terminals
•For future servicing, leave some slack in the connecting wires.
Conduit cover
Remark:
*A disconnect switch is required.
Check the local code.
**Use a ring tongue termi- nal in order to connect a ground wire to terminal.
Power supply 208/230 V AC, 1phase 2wires. 60 Hz
INDOOR UNIT | Grouding | |
Terminal block | ||
terminal** |
Disconnect switch*
208/230 V AC 1phase, 60 Hz
OUTDOOR UNIT
Terminal | block 1 |
Terminal block 2 |
|
Less than 3/8 in. | Less than | |
(10 mm) | (30 mm) | |
Lock nut | Elbow joint | |
(for right, left, or | ||
Conduit pipe or | ||
downward piping) | ||
elbow joint | Fig. 2 | |
Fig. 1 |
19/32 in.
1 in. (15 mm)
(25 mm)
Ground | Grouding terminal** |
Lead |
|
wire | Hook |
• Make ground wire a little longer than |
|
| ||
others. (More than |
| Conduit cover | ||
| Fig. 3 |
| Fig. 4 | |
|
|
| Corner box | |
|
|
| 1 in. | |
|
|
| (25 mm) | |
| Box |
|
| |
Remove panel for | Remove panel for |
| Remove panel for | |
piping on left side of | piping on bottom left |
| ||
Remove panel for | piping on right side of | |||
unit | side of unit | |||
|
| piping on bottom side | unit | |
| Fig. 5 | of unit | Fig. 6 | |
|
|