5. RELOCATION AND MAINTENANCE

5. RELOCATION AND MAINTENANCE

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

Removal procedure

1)Remove the two screws that attach the panel assembly.

 5HPRYHWKHSDQHODVVHPEO\%HVXUHWRUHPRYHLWVERWWRPHQG¿UVW

Installation procedure

1)Install the panel assembly following the removal procedure in reverse.

2)Be sure to press the positions as indicated by the arrows in order to attach the assembly completely to the unit.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate.

When releasing the corner part, release both left and right bottom corner part of LQGRRUXQLWDQGSXOOLWGRZQZDUGDQGIRUZDUGDVVKRZQLQWKH¿JXUHRQWKHULJKW

If the above method cannot be used

Remove the front panel. Then, insert hexagonal wrenches into the square holes on WKHOHIWDQGULJKWVLGHVRIWKHXQLWDQGSXVKWKHPXSDVVKRZQLQWKHIROORZLQJ¿JXUH The bottom of the indoor unit lowers and releases the hooks.

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmosphere.

1)Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

2)Fully close the stop valve on the liquid pipe side of the outdoor unit.

3)Close the stop valve on the gas pipe side of the outdoor unit almost completely

so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 lbf/in.2 [0 kgf/cm2]).

4)Start the emergency COOL operation.

To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)

5)Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 lbf/in2 [0.5 to 0 kgf/cm2]).

6)Stop the emergency COOL operation.

Press the E.O. SW twice to stop the operation.

Push

Lower

Square hole