835961-UIM-D-0213

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE type oils, and the higher pressures of R-410A.

Manifold sets should be 800 psig high side and 250 psig low side with 550 psig low side restart.

All hoses must have a 700 psig service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers) must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

A liquid-line filter drier is required on every unit.

LIMITATIONS

The unit should be installed in accordance with all National, State, and Local Safety Codes and the limitations listed below:

1.Limitations for the indoor unit, coil, and appropriate accessories must also be observed.

2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.

3.The maximum and minimum conditions for operation must be observed to assure a system that will give maximum performance with minimum service.

4.The maximum allowable line length for this product is 75 feet.

AIR TEMPERATURE AT

AIR TEMPERATURE AT

 

OUTDOOR COIL, °F

 

 

INDOOR COIL, °F

 

 

 

 

 

Min.

Max.

Min.

Max.

DB

 

DB

DB

 

DB

WB

 

DB

WB

 

DB

Cool

 

Heat

Cool

 

Heat

Cool

 

Heat

Cool

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

50

 

-10

115

 

75

57

 

501

72

 

80

1.Operation below this temperature is permissible for a short period of time, during morning warm-up.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the condenser coil, for air discharge, and for service access. See Figure 1.

NOTICE

For multiple unit installations, units must be spaced a minimum of 24 inches apart (coil face to coil face).

If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit.

Provide an adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-22 unit, it is required that the outdoor unit, indoor coil, and metering device all be replaced. The following steps should be performed in order to insure proper system operation and performance. Line-set change out is also recommended.

1.Change-out of the indoor coil to an approved R-410A coil/ condens- ing unit combination with the appropriate metering device.

2.Change-out of the line-set when replacing an R-22 unit with an R410-A unit is highly recommended to reduce cross-contamination of oils and refrigerants.

3.If change-out of the line set is not practical, then the following pre- cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions, and for corrosion.

Determine if there are any low spots which might be serving as oil traps.

Flush the line set with a commercially available flush kit to remove as much of the existing oil and contaminants as possible.

Install a suction line filter-drier to trap any remaining contami- nants, and remove after 50 hours of operation.

4.If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction-line filter drier in the suction-line is required, in addition to the factory installed liq- uid-line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction-line and liquid-line driers. After a total of 10 hours run time where the suction-line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suction-line drier. Never leave a suction-line drier in the system longer than 50 hours of run time.

60” OVERHEAD CLEARANCE

10” CLEARANCE AROUND PERIMETER

NOTES:

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. MINIMUM 24” UNIT TO UNIT CLEARANCE.

MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE

WEATHERPROOF

DISCONNECT

SWITCH

CONTROL

ACCESS

PANEL

THERMOSTAT

NEC CLASS 1 WIRING

NEC CLASS 2 WIRING

TO FURNACE OR

AIR HANDLER

TERMINAL BLOCK

TO INDOOR COIL

SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT

FIGURE 1: Typical Installation with Required Clearances

2

Johnson Controls Unitary Products

Page 2
Image 2
Thermo Products Section III Unit Installation, Requirements For Installing/Servicing R-410A Equipment, Limitations