16. Specifications
Notes:*1 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27 °C DB/19 °C WB Outdoor: 35 °C DB
*2 The operating noise is the data that was obtained in an anechoic room.
Both indoor and outdoor temperatures assume a relative humidity of 30 - 80%.
Contact your retailer if the unit is to be used at an outdoor dry bulb temperature of 5°C or lower.
Power source
Cooling capacity*1 kW
Height mm
Dimension Width mm
Depth mm
Net weight kg
Fan Airflow rate (Low-Middle-High) m3/min
Noise level*2 dB(A)
Filter
PFD-P250VM-A
28
1200
350
160
59
Item Model
PFD-P·VM-A series
Dry bulb temperature
Wet bulb temperature
Indoor
12 °C~24 °C
Outdoor
5 °C~43 °C
17. Warranty and Servicing
ss
ss
sIn addition to daily checks (eg cleaning of filters), periodic maintenance and checks by a skilled technician are required to ensure that the unit is maintained
in a good condition for a long period of time, and that it may be used with confidence.
Check Frequency for the standard maintenance and checks, and the Maintenance Frequency associated with periodic checks are as follows.
<Maintenance and Check Frequencies>
1. Preventative Maintenance Guidelines
The following maintenance frequencies are a guide to the replacement of parts as based on the results of periodic checks and scheduled frequency of repairs. They do
not imply that replacement is always necessary in accordance with the maintenance frequency (except for consumables such as fan belts).
Note that the following does not indicate maintenance periods.
Table 2 Maintenance and Check Frequencies
2. Cautions
The maintenance and check frequencies in the table above are applicable under the following conditions of use.
A. Normal conditions of use, with infrequent starting and stopping (varies with model, however interval of starting and stopping would normally use is generally six times
or less per hour).
B. 24 hours using.
The maintenance interval may need to be reduced under any of the following conditions.
1Use under conditions of high temperature or humidity, or in locations in which variations in temperature and humidity are considerable.
2Use in locations in which power supply variations (e.g. voltage, frequency, waveform distortion) are considerable. Note that the unit cannot be used outside the
allowable range of conditions.
3Use in locations subject to considerable vibration and shock.
4Use in an atmosphere containing toxic gases (e.g. dust, salt, sulfuric acid vapor, hydrogen sulfide) or oil mist etc.
Unexpected events may occur even when periodic checks are implemented based on the check frequency. In such cases the appropriate repairs outside the period of
the warranty are chargeable.
Unit Parts
Fan motor
Bearing
Fan belt
Air filter
Drain pan
Drain hose
Linear expansion valve
Heat exchanger
Float switch
Display lamp
Compressor
Fan motor
Linear expansion valve
Heat exchanger
Pressure switch
Inverter cooling fan
Check frequency
6 months
3 months
6 months
1 year
6 months
1 year
6 months
1 year
Outdoors
(air-cooled) Indoors
Maintenance frequency
40,000 hours
40,000 hours
8,000 hours
5 years
8 years
8 years
25,000 hours
5 years
25,000 hours
8,000 hours
40,000 hours
40,000 hours
25,000 hours
5 years
25,000 hours
40,000 hours
Ordinarily check
Maintenance check
Remarks
Replenish oil annually.
Consumable part
Check interval are affected by local conditions.
PFD-P500VM-A
56
1800
480
320
64
3N~/380-415V (50Hz), 400-415V (60Hz)
1895
800
Long life filter