INSTALLATION PREPARATION

624WBPF Woodburning Fireplace

INSTALLATION PREPARATION

 

 

Survey the planned location for the fireplace for overhead plumbing or electrical wires, etc., that might complicate the installation or endanger persons installing or cleaning the chimney. Avoid a location where the chimney cap will be near abrupt changes in the roof shape, nearby wall or embankments, under or near trees or above the roof of a single story wing of a two story building. Figure 6. All these conditions can cause turbulence or pressure conditions that can cause poor chimney draft and smoke spillage from the fireplace opening. Elbows may be used to offset the chimney to avoid obstructions or to locate the chimney cap in a preferred location. Refer to the sections of this manual pertaining to chimney offsets for instructions on proper elbow usage. Poor installation or location of the chimney cap and/or components can cause wind blown rain to enter the chimney.

If the fireplace is to be installed on an outside wall, the surrounding walls (chase) should be insu- lated. Failure to insulate the fireplace from outside temperatures will cause heat loss through and around the fireplace.

Single Story Installation with Attic Space

Chimney Cap

Multiple Story Installation

 

Flue Outlet Height

Storm Collar

3’ Min. or 2’ Above

any Point within 10’

 

Flashing

 

 

Attic Space

 

See Table

 

1 for Roof

Chimney Cap Single Story Installation with Attic Space

Storm Collar (Included with cap)

Flashing

Flue Outlet Height

3 ft. Min.

Attic Space

Opening Size

14’ Min.

Firestop Spacer

Multiple Story Installation Refer to Table 1 for Roof Opening Size

17” Square

(1Z\x” Air space

Clearance to

Opening in

Combustibles)

Joist

Chimney

 

 

Sections

 

2” Min. Air Space

 

Clearance Between

 

Combustibles and

 

Chimney

 

FP2347

Figure 4

 

 

Preferred

 

Location

 

Poor

 

Location

17” Square Open- ing in Joist

Max. Instal-

lation Height

-

86 ft.

Support Re- quired Every

35 ft. 17” Square Opening in Joist

17” Square Manual backgroundManual background Opening in Joist Manual backgroundManual background

Firestop

Spacer (2”

Air Space Third Floor

Clearance to

Combustibles) Area

2” Clearance to Combustibles (Min.) Manual background

Firestop

Second

Floor Area

Spacer

Firestop

Spacer

First Floor

Area

Figure 5

FP2348

Figure 6

FP1882

53D9052

Page 8
Image 8
Monessen Hearth manual 624WBPF Woodburning Fireplace, Installation Preparation, 53D9052, Multiple Story Installation