Monessen Hearth TPB24, TPB30, TPB18 Floor Clearance, Heater in Fireplace or Firebox Combustible

Models: TPB18 TPB30 TPB24

1 42
Download 42 pages 20.27 Kb
Page 16
Image 16
FLOOR CLEARANCE

FLOOR CLEARANCE

The gas log heater must be installed at least 13/8" above any combustible flooring material, such as carpeting or tile, which is closer than 14" to the base of the fireplace. The minimum distance must be maintained from the top surface of carpeting, tile, etc. See Figure 11.

OR

The gas log heater may be installed nearer to the floor if a minimum of 14" of noncombustible material such as slate or marble is installed between the base of the fireplace and the combustible flooring. See Figure 12.

Heater in

Fireplace or

Firebox

Combustible

Material

13/8" Minimum

Figure 11 - Minimum Clearance above Combustible Flooring

This Distance May Now Be Less than 13/8"

Heater in

Fireplace or

Firebox

Combustible

Material

Heater in14" Minimum MaterialThis Distance May Now Be Less than 13/8"

Figure 12 - Minimum Clearance above Combustible Flooring with

Noncombustible Material Installed at Base of Fireplace

16

70D0004

Page 16
Image 16
Monessen Hearth TPB24, TPB30, TPB18 manual Floor Clearance, Heater in Fireplace or Firebox Combustible, Material 13/8 Minimum