Moxa Technologies 6110 user manual 4-10, IP address

Models: 6110

1 52
Download 52 pages 37.65 Kb
Page 36
Image 36
IP address.

Advanced Modbus Settings

Setting

Value

Notes

 

Enable (Default)

Select Enable when

Auto Slave Unit ID

multiple Modbus devices

 

 

are accessible at the same

Disable

 

 

IP address.

1

 

 

 

 

10 to 3000 ms

This parameter is active

Character Timeout

when the attached serial

(default = 100 ms)

device is set to

 

 

Modbus/RTU.2

 

 

Allows you to configure

 

10 to 3000 ms

the message timeout for

Message Timeout

communication between

(default = 1000 ms)

 

connected Ethernet or

 

 

 

 

serial Modbus devices.

 

 

This parameter is active

 

 

when the Modbus

Modbus/TCP Exception

default = 502

Gateway connects a

Modbus/TCP Master with

 

 

 

 

Modbus serial slave

 

 

devices.3

 

Additional Information

1.Modbus/TCP protocol contains a “Unit ID” field to identify multiple Modbus slave devices accessible at a single IP address. When the Modbus/TCP command contains a Unit ID, the Modbus Gateway can pass the Unit ID to Modbus serial devices. This allows you to link to multiple serial devices with a Modbus Gateway. Some PLCs assume that each IP connects to only one device. In these cases, the Unit ID can be set “0,” but you must manually assign a Unit ID (between 1 and 247) to the connected serial device. However, each Modbus Gateway can connect to only one serial device.

This setting is valid when [Attached Serial Device type] is set to [Modbus RTU Slave ] or [Modbus ASCII Slave].

Enable: Uses the Unit ID in the Modbus/TCP packet. This is the default setting.

Disable: Uses the predefined Unit ID instead of Modbus/TCP’s.

ID:

The predefined Unit ID value, ranging from 1 to 247, which is valid

4-10

Page 36
Image 36
Moxa Technologies 6110 user manual 4-10, IP address