CHAPTER II

CHAPTER II

HEATER INSTALLATION

1.GENERAL INSTALLATION INFORMATION AND REQUIREMENTS

The required minimum clearances to combustible surfaces are illustrated in Figure 2 and Table 3. As shown on Figure 2, the front of the heater is installed at the minimum required clearance to

combustible surfaces and toward open space, and then the other sides must have a minimum clearance of 16 inches to combustible surfaces.

EXHAUST

CEILING

 

 

VENT

 

 

 

 

 

 

 

16”

 

14”

 

 

MINIMUM

 

MINIMUM

OPEN

 

 

 

 

 

 

 

 

WORKSHOP DOOR

 

30

 

 

16”

 

 

 

 

MINIMUM

 

 

 

HEATER

 

 

 

 

WALL BRACK-

 

14-1/2”

 

ET

 

 

 

 

48”

 

 

 

MINIMUM

NOTE:

 

 

 

 

 

 

 

 

1.

ONLY FLUE SIDE OF HEATER CAN

 

 

 

 

BE ELEVATED (30o).

 

 

 

2.

HEATER SIDE REFLECTOR MUST

 

 

 

 

BE HORIZONTAL.

FLOOR LINE

Figure 2. Installation Clearances to Combustible Surfaces

Table 3. Installation, Ventilation and Mounting Information

 

BTU/HR. RATING

NORMAL

 

 

 

 

MODEL

GAS

 

MOUNTING

CLEARANCES TO COMBUSTIBLE SURFACES

NO.

NAT.

L.P.

POSITION

TOP

SIDES

BACK

BELOW

MH/HS25NG

25,000

30o

14”

16”

16”

48”

MH/HS25LP

22,000

 

30o

14”

16”

16”

48”

 

 

 

 

 

 

 

 

 

Model # MH25NG/LP

HS25NG/LP

E5

Installation instructions and Owner’s Manual