Installing the UPS System

23.After wiring the UPS system to the facility power and critical load, be sure to ground the system according to local and/or national electrical wiring codes. DO NOT bond the neutral to ground.

24.If wiring interface connections, proceed to paragraph 3.2.5; otherwise, proceed to Step 25.

25.When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware.

26.Close the control panel door and secure with the retained hardware.

27.Reinstall the door removed in paragraph 3.2.1 and secure with the retained hardware.

28.Close the door and secure the latch.

3.2.5Installing Interface Connections

3.2.5.1 TB1 and TB2 Connections

NOTE When installing interface wiring for TB1 and TB2 connections, conduit must be installed between each device and the UPS cabinet.

To install wiring to connections:

1.Verify the UPS system is turned off and all power sources are removed. (See Chapter 10, “UPS Operating Instructions,” for shutdown instructions.)

2.If not already open, unfasten the front door latch and swing the door open (see Figure 3-1).

3.If not already removed, remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. Retain the hardware for later use.

4.Remove the screws securing the control panel door and swing the door open. Retain the hardware for later use.

5.Remove the screws securing the top internal safety shield panel. Remove the panel to gain access to the TB1 and TB2 terminal blocks, and the top conduit landing plate (see Drawing 164201535-8 starting on page A-33). Retain the hardware for later use.

6.If installing interface wiring from the bottom of the cabinet, proceed to Step 7; otherwise, proceed to Step 8.

7.Remove the screws securing the bottom internal safety shield panel and remove the panel to gain access to the bottom conduit landing plate.

3-8

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C

Page 30
Image 30
Powerware 9390 operation manual Installing Interface Connections, 5.1 TB1 and TB2 Connections

9390 specifications

The Powerware 9390 is a high-performance uninterruptible power supply (UPS) designed for critical applications in data centers, telecommunications, and other industries requiring maximum uptime. This UPS system is renowned for its durability, efficiency, and advanced technological features, making it an ideal choice for environment-sensitive operations.

One of the standout characteristics of the Powerware 9390 is its modular architecture. This design allows for scalability, enabling businesses to tailor the power supply to fit their specific needs. Users can add or remove power modules as demand fluctuates, ensuring optimal performance without overspending on unnecessary capacity. The system is available in various power ratings, typically ranging from 40 kVA to 750 kVA.

Among the key technologies utilized in the Powerware 9390 is the Advanced Battery Management (ABM) system. This innovative feature helps extend battery life by monitoring and optimizing charging cycles. The ABM technology uses an intelligent three-stage charging process, significantly reducing battery wear while ensuring high availability of power during outages. This enhancement not only improves reliability but also lowers maintenance costs over time.

Energy efficiency is another hallmark of the Powerware 9390, as it incorporates double-conversion technology to maintain voltage stability. This ensures that sensitive electronic equipment is protected from surges and fluctuations in power supply. Additionally, the UPS offers high input power factor and low harmonic distortion, contributing to overall energy savings while minimizing the environmental impact.

The Powerware 9390 is equipped with advanced monitoring and management features that allow users to maintain complete control over their power infrastructure. An intuitive LCD display provides real-time metrics on system performance, battery status, and operational logs. Furthermore, the UPS can be integrated with network management systems, enabling remote monitoring and management via web interfaces.

In terms of safety characteristics, the Powerware 9390 adheres to rigorous industry standards, ensuring that it provides reliable performance under various operating conditions. Its robust construction and redundant components further enhance reliability, making it a popular choice in mission-critical environments.

In conclusion, the Powerware 9390 stands out as a leader in the UPS market, combining modular scalability, advanced battery management, energy efficiency, and robust safety features. Its ability to adapt to the needs of dynamic organizations while providing reliable power protection makes it an invaluable asset for any critical application. With its state-of-the-art technologies, businesses can depend on the Powerware 9390 for continuity, efficiency, and peace of mind.