Installation Information

23.Parallel system UPM and system bypass input feeds must come from the same source.

24.Parallel UPM input wiring size requirements and output wiring size requirements from the UPMs to the tie cabinet or distribution panel are the same as listed in Table E through Table H.

25.See Drawing 164201535---7 for UPM terminal locations and Table I or Table J for termination requirements.

26.Setup of the CAN Bridge card for parallel operation must be performed by an authorized Powerware Customer Service Engineer. Contact service to schedule a date.

27.For parallel system circuit breaker ratings, see appropriate information in Table O.

28.For parallel system ratings, see the appropriate information in Table P through Table S.

Table O. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)

 

 

Circuit Breaker Ratings

 

 

 

UPM Model

Configuration

 

 

Output Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

 

 

480V

 

 

 

 

 

 

 

 

 

 

 

MOB

MIS

MBP

MOB

MIS

MBP

 

 

 

 

 

 

 

 

 

1+1

150

150

150

70

70

70

 

 

 

 

 

 

 

 

9390---40

2+0 and 2+1

150

300

300

70

150

150

 

 

 

 

 

 

 

3+0 and 3+1

150

450

450

70

200

200

 

 

 

 

 

 

 

 

 

 

4+0

150

600

600

70

250

250

 

 

 

 

 

 

 

 

 

1+1

200

200

200

80

80

80

 

 

 

 

 

 

 

 

9390---50

2+0 and 2+1

200

350

350

80

175

175

 

 

 

 

 

 

 

3+0 and 3+1

200

600

600

80

250

250

 

 

 

 

 

 

 

 

 

 

4+0

200

700

700

80

350

350

 

 

 

 

 

 

 

 

 

1+1

225

225

225

100

100

100

 

 

 

 

 

 

 

 

9390---60

2+0 and 2+1

225

500

500

100

200

200

 

 

 

 

 

 

 

3+0 and 3+1

225

700

700

100

300

300

 

 

 

 

 

 

 

 

 

 

4+0

225

1000

1000

100

400

400

 

 

 

 

 

 

 

 

 

1+1

300

300

300

125

125

125

 

 

 

 

 

 

 

 

9390---80

2+0 and 2+1

300

600

600

125

250

250

 

 

 

 

 

 

 

3+0 and 3+1

300

1000

1000

125

400

400

 

 

 

 

 

 

 

 

 

 

4+0

300

1200

1200

125

500

500

 

 

 

 

 

 

 

 

 

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201535---5

 

 

SHEET: 11 of 16

 

 

 

 

REVISION:

B

 

DATE:

093004

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual

S

164201535 Rev C

 

A-21

Page 169
Image 169
Powerware 9390 operation manual Circuit Breaker Ratings

9390 specifications

The Powerware 9390 is a high-performance uninterruptible power supply (UPS) designed for critical applications in data centers, telecommunications, and other industries requiring maximum uptime. This UPS system is renowned for its durability, efficiency, and advanced technological features, making it an ideal choice for environment-sensitive operations.

One of the standout characteristics of the Powerware 9390 is its modular architecture. This design allows for scalability, enabling businesses to tailor the power supply to fit their specific needs. Users can add or remove power modules as demand fluctuates, ensuring optimal performance without overspending on unnecessary capacity. The system is available in various power ratings, typically ranging from 40 kVA to 750 kVA.

Among the key technologies utilized in the Powerware 9390 is the Advanced Battery Management (ABM) system. This innovative feature helps extend battery life by monitoring and optimizing charging cycles. The ABM technology uses an intelligent three-stage charging process, significantly reducing battery wear while ensuring high availability of power during outages. This enhancement not only improves reliability but also lowers maintenance costs over time.

Energy efficiency is another hallmark of the Powerware 9390, as it incorporates double-conversion technology to maintain voltage stability. This ensures that sensitive electronic equipment is protected from surges and fluctuations in power supply. Additionally, the UPS offers high input power factor and low harmonic distortion, contributing to overall energy savings while minimizing the environmental impact.

The Powerware 9390 is equipped with advanced monitoring and management features that allow users to maintain complete control over their power infrastructure. An intuitive LCD display provides real-time metrics on system performance, battery status, and operational logs. Furthermore, the UPS can be integrated with network management systems, enabling remote monitoring and management via web interfaces.

In terms of safety characteristics, the Powerware 9390 adheres to rigorous industry standards, ensuring that it provides reliable performance under various operating conditions. Its robust construction and redundant components further enhance reliability, making it a popular choice in mission-critical environments.

In conclusion, the Powerware 9390 stands out as a leader in the UPS market, combining modular scalability, advanced battery management, energy efficiency, and robust safety features. Its ability to adapt to the needs of dynamic organizations while providing reliable power protection makes it an invaluable asset for any critical application. With its state-of-the-art technologies, businesses can depend on the Powerware 9390 for continuity, efficiency, and peace of mind.