Installing Options and Accessories

NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Powerware Customer Service Engineer. Contact service to schedule a date.

9.To check the operation of the RMP, ensure that the UPS is supplying the load via inverter or bypass. If the indicators on the RMP show the appropriate status, then it is operating correctly.

If the communication link between the UPS and the RMP is not present, the RMP performs a self-test (all indicators flash and the horn beeps at one-second intervals). If the self-test occurs, check all harness connectors and the fuse for proper seating. If all connections are secure but the RMP continues to self-test, replace the fuse with the spare included in the hardware kit. If a fuse replacement does not correct the problem, contact your Powerware service representative for verification that the RMP is working correctly.

10.To test the indicator lamps, press and hold the horn silence pushbutton for

3 seconds. All lamps should illuminate, and the horn sounds continuously until you release the pushbutton.

6.5 Installing a Relay Interface Module

NOTE Only one system monitoring device can be connected to the Hot Sync CAN Bridge Card at one time (see Table 6-1).

To install RIM wiring, perform the following procedure:

1.Verify the UPS system is turned off and all power sources are removed. See Chapter 10, “UPS Operating Instructions,” for shutdown instructions.

2.Perform procedures listed in paragraphs 6.1 and 6.2.

NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the wall. Do not use hollow wall anchors.

3.Securely mount the RIM at the desired location. See drawing 164201535-12 for mounting hole locations.

NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the device and the UPS cabinet.

NOTE Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit holes (see Drawing 164201535-6 on page A-27).

4.Remove the X-Slot conduit landing plate from the UPS cabinet to drill or punch conduit holes (see Drawing 164201535-6 on page A-27).

5.Reinstall the conduit landing plate.

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C

6-5

Page 49
Image 49
Powerware 9390 operation manual Installing a Relay Interface Module

9390 specifications

The Powerware 9390 is a high-performance uninterruptible power supply (UPS) designed for critical applications in data centers, telecommunications, and other industries requiring maximum uptime. This UPS system is renowned for its durability, efficiency, and advanced technological features, making it an ideal choice for environment-sensitive operations.

One of the standout characteristics of the Powerware 9390 is its modular architecture. This design allows for scalability, enabling businesses to tailor the power supply to fit their specific needs. Users can add or remove power modules as demand fluctuates, ensuring optimal performance without overspending on unnecessary capacity. The system is available in various power ratings, typically ranging from 40 kVA to 750 kVA.

Among the key technologies utilized in the Powerware 9390 is the Advanced Battery Management (ABM) system. This innovative feature helps extend battery life by monitoring and optimizing charging cycles. The ABM technology uses an intelligent three-stage charging process, significantly reducing battery wear while ensuring high availability of power during outages. This enhancement not only improves reliability but also lowers maintenance costs over time.

Energy efficiency is another hallmark of the Powerware 9390, as it incorporates double-conversion technology to maintain voltage stability. This ensures that sensitive electronic equipment is protected from surges and fluctuations in power supply. Additionally, the UPS offers high input power factor and low harmonic distortion, contributing to overall energy savings while minimizing the environmental impact.

The Powerware 9390 is equipped with advanced monitoring and management features that allow users to maintain complete control over their power infrastructure. An intuitive LCD display provides real-time metrics on system performance, battery status, and operational logs. Furthermore, the UPS can be integrated with network management systems, enabling remote monitoring and management via web interfaces.

In terms of safety characteristics, the Powerware 9390 adheres to rigorous industry standards, ensuring that it provides reliable performance under various operating conditions. Its robust construction and redundant components further enhance reliability, making it a popular choice in mission-critical environments.

In conclusion, the Powerware 9390 stands out as a leader in the UPS market, combining modular scalability, advanced battery management, energy efficiency, and robust safety features. Its ability to adapt to the needs of dynamic organizations while providing reliable power protection makes it an invaluable asset for any critical application. With its state-of-the-art technologies, businesses can depend on the Powerware 9390 for continuity, efficiency, and peace of mind.