Installing the UPS System

3.2.5.3 X-Slot Connections

NOTE LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or customer.

NOTE When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay.

For installation and setup of an X-Slot card, please contact Powerware (see page 1-6). To install wiring for connections:

1.If not already installed, install the LAN and telephone drops.

2.Unfasten the front door latch and swing the door open.

3.Remove the UPS cabinet X-Slot conduit landing plate to drill or punch conduit holes (see Drawing 164201535-6 on page A-27).

4.Reinstall the conduit landing plate and install the conduit.

5.Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards.

6.When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware.

7.Close the control panel door and secure with the retained hardware.

8.Reinstall the door removed in Step 3 or paragraph 3.2.1 and secure with the retained hardware.

9.Close the door and secure the latch.

10.Refer to the manual supplied with the X-Slot card for user instructions.

3.2.6 Installing Accessories and Parallel System Control Wiring

To install an optional Remote Emergency Power-Off Control, see Chapter 5, “Installing a Remote Emergency Power-Off Control.” To install optional accessories, see Chapter 6, “Installing Options and Accessories.” To install parallel system control wiring, see Chapter 6, “Installing Options and Accessories.”

3.3 Initial Startup

Startup and operational checks must be performed by an authorized Powerware Customer Service Engineer, or the warranty terms as specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact service in advance (usually a two-week notice is required) to reserve a preferred startup date.

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C

3-11

Page 33
Image 33
Powerware 9390 operation manual Initial Startup, Installing Accessories and Parallel System Control Wiring

9390 specifications

The Powerware 9390 is a high-performance uninterruptible power supply (UPS) designed for critical applications in data centers, telecommunications, and other industries requiring maximum uptime. This UPS system is renowned for its durability, efficiency, and advanced technological features, making it an ideal choice for environment-sensitive operations.

One of the standout characteristics of the Powerware 9390 is its modular architecture. This design allows for scalability, enabling businesses to tailor the power supply to fit their specific needs. Users can add or remove power modules as demand fluctuates, ensuring optimal performance without overspending on unnecessary capacity. The system is available in various power ratings, typically ranging from 40 kVA to 750 kVA.

Among the key technologies utilized in the Powerware 9390 is the Advanced Battery Management (ABM) system. This innovative feature helps extend battery life by monitoring and optimizing charging cycles. The ABM technology uses an intelligent three-stage charging process, significantly reducing battery wear while ensuring high availability of power during outages. This enhancement not only improves reliability but also lowers maintenance costs over time.

Energy efficiency is another hallmark of the Powerware 9390, as it incorporates double-conversion technology to maintain voltage stability. This ensures that sensitive electronic equipment is protected from surges and fluctuations in power supply. Additionally, the UPS offers high input power factor and low harmonic distortion, contributing to overall energy savings while minimizing the environmental impact.

The Powerware 9390 is equipped with advanced monitoring and management features that allow users to maintain complete control over their power infrastructure. An intuitive LCD display provides real-time metrics on system performance, battery status, and operational logs. Furthermore, the UPS can be integrated with network management systems, enabling remote monitoring and management via web interfaces.

In terms of safety characteristics, the Powerware 9390 adheres to rigorous industry standards, ensuring that it provides reliable performance under various operating conditions. Its robust construction and redundant components further enhance reliability, making it a popular choice in mission-critical environments.

In conclusion, the Powerware 9390 stands out as a leader in the UPS market, combining modular scalability, advanced battery management, energy efficiency, and robust safety features. Its ability to adapt to the needs of dynamic organizations while providing reliable power protection makes it an invaluable asset for any critical application. With its state-of-the-art technologies, businesses can depend on the Powerware 9390 for continuity, efficiency, and peace of mind.