29.Required parallel system wiring length should be in accordance with the following rule, as referenced to the diagram below, to ensure approximately equal current sharing, when in static bypass mode:

(Total length of 1A + 1B) ￿ (Total length of 2A + 2B) ￿ (Total length of 3A + 3B) ￿￿(Total length of 4A + 4B)

This rule has a tolerance of approximately H10% for the combined input and output wire lengths.

If installing only two UPMs in a fully redundant system, this requirement is no longer required, as each UPM is capable of supporting the full bypass requirement. However, this would preclude future expansion.

Bypass inputs to UPMs

1A

2A

3A

4A

UPM 1

Battery

UPM 2

Battery

UPM 3

Battery

UPM 4

Battery

Outputs from UPMs

1B

2B

3B

4B

 

 

 

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201535---5

 

 

SHEET: 16 of 16

 

 

 

 

 

REVISION: B

 

DATE:

093004

 

 

 

 

 

 

 

 

 

 

 

A-26

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C