Powerware 9390 operation manual Sheet 13

Models: 9390

1 206
Download 206 pages 4.93 Kb
Page 171
Image 171

Installation Information

Table Q. INPUT/OUTPUT Ratings for Powerware 9390---50 Parallel System

 

 

Configuration

 

 

Units

 

Rating 50/60 Hz

 

 

 

 

 

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

kVA

 

50

50

 

 

kW

 

45

45

 

 

 

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

VOLTS

 

208

480

 

Output

 

VOLTS

 

208

480

 

 

 

 

 

 

 

 

AC Input from UPM

 

Amps

 

139

60

 

Full Load Current for each Module

 

 

All

(3) Phases, (1) Neutral, (1) Ground

D

 

 

 

 

 

 

 

 

 

Minimum Conductor Size for each Module

AWG or

 

See Table E through

 

 

 

 

 

kcmil

 

Table H for wire size.

 

Number per Phase for each Module

 

 

 

 

(each)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

Full Load Current

Amps

 

139

60

1+1

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

G

Amps

 

139

60

 

 

 

Full Load Current

 

 

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

2+0

Full Load Current

Amps

 

278

120

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

and

 

 

 

 

 

 

AC Output to Critical Load

 

 

 

 

 

2+1

G

 

 

 

 

 

Full Load Current

Amps

 

278

120

 

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

3+0

Full Load Current

Amps

 

417

180

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

and

 

 

 

 

 

 

AC Output to Critical Load

 

 

 

 

 

3+1

G

 

 

 

 

 

Full Load Current

Amps

 

417

180

 

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

F

 

 

 

 

 

Full Load Current

Amps

 

556

240

4+0

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

G

 

 

 

 

 

 

 

 

 

 

Full Load Current

Amps

 

556

240

 

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

NOTE: Callout letters D, F, and G map to drawing 164201535 ---4, sheets 3 of 5, 4 of 5, and 5 of 5.

 

 

DESCRIPTION:

POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201535---5

 

 

SHEET: 13 of 16

 

 

 

 

REVISION:

B

 

DATE:

093004

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual

S

164201535 Rev C

 

A-23

Page 171
Image 171
Powerware 9390 operation manual Sheet 13