DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the Output Terminal Lugs.. The voltages at the terminals are depen- dent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3Ø 220/127 Output Terminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 22.

Figure 22. Voltage Selector Switch 240/139V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 22.

3Ø 200V/1Ø115V Output Terminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 25.

Use this position for 3Ø-200 or 1Ø115V.

Figure 25. Voltage

Selector Switch 240/139V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 26.

Figure 26. Output Terminal Lugs

3Ø-200V/115V Connections

3.Turn the voltage regulator knob (Figure 24) clockwise to increase voltage output, turn counterclockwise to decrease voltage output.

Figure 23. Output Terminal Lugs

 

To achieve a 3Ø 200V output

3Ø 220/127VThree Phase Connections

NOTE

the voltage selector switch

3. Turn the voltage regulator knob (Figure 23) clockwise to

must be in the 3Ø-240/139

 

increase voltage output, turn counterclockwise to

 

position and the voltage

decrease voltage output.

 

regulator must be adjusted to

 

 

200V.

Figure 24. Voltage Regulator Knob (139V/240V)

PAGE 32 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)