Multiquip DCA-125USJ 50 HZ- Generator SHUT-DOWN Procedure, Emergency Shutdown Procedure

Models: DCA-125USJ

1 86
Download 86 pages 19.47 Kb
Page 42
Image 42

DCA-125USJ (50 HZ)— GENERATOR SHUT-DOWN PROCEDURE

CAUTION:

Emergency Shutdown Procedure

NEVER stop the engine suddenly except in an emergency. DO NOT use the emergency stop switch a as method of shutting down the generator. This switch is ONLY to be used in the event of an emergency.

Shutdown Procedure

To shutdown the generator use the following procedure:

1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 39 to the OFF position.

3.Let the engine cool by running it for 3-5 minutes with no load applied.

4.Place the MPEC Control Switch (Figure 55) to the OFF/RESET position.

1.To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 39) circuit breakers to OFF position.

2.Place the MPEC Control Switch switch (Figure 55) to the OFF/RESET position.

Figure 55. MPEC Control Switch (Off/Reset)

5.Verify that the all status LED on the MPEC display are OFF (not lit).

6.Remove all loads from the generator.

PAGE 42 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)

Page 42
Image 42
Multiquip operation manual DCA-125USJ 50 HZ- Generator SHUT-DOWN Procedure, Emergency Shutdown Procedure