DCA-400SSV— OPERATION AND PARTS MANUAL — REV. #0 (04/19/06) — PAGE 29
1
Maximum Amps
Table 10 shows the

maximum

amps the generator can pro-
vide. DO NOT exceed the maximum amps as listed.
How to Read the Output Terminal Gauge.
The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.
When the voltage change-over board is jumpered for 3Ø,
240V operation (See Figures 16 and17), place the

AC Volt-

meter Change-Over

Switch

(See Figures 18 and 19) to the
W-U position and the

AC Ammeter Change-Over Switch

(Figure 18) to the U or W position to read the output on the
selected leg.
Figure 15. Voltage Change-Over Board
240V Configuration
Figure 16. AC Voltmeter
Change-Over Switch
Figure 17. AC Voltmeter Gauge
(Volt reading on W-U Lug)
Figure 19. AC Ammeter
(Amp reading on U lug)
Figure 18. AC Ammeter
Change-Over Switch
The

ammeter

gauge will only
show a reading when the
Output Terminal Lugs
are
connected to a load and in use.
NOTE
DCA-400SSV— GENERATOR OUTPUTS/ GAUGE READING
spmAmumixaMrotareneG.01elbaT
ledoMVSS004-ACD
egatloVdetaRspmAmumixaM
esahPelgniS
tloV021 )eriw4(spma9.888
esa
hPelgniS
tloV042 )eriw4(spma4.444
esahPeerhT
tloV042 spma3.269
esahPeerhT
tloV084 spma1.184