DCA-45USI — GENERAL INFORMATION
DCA-45USI FAMILIARIZATION
Generator
The MQ Power Model
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
zTachometer
zWater Temperature Gauge/ Alarm Lamp
zOil Pressure Gauge/ Alarm Lamp
zCharging Ammeter Gauge
z
zPanel Light
zPanel Light Switch
zIgnition/Preheat Switch
zFuel Gauge
zFuel Filter Water Level Alarm Lamp
Generator Control Panel
The “Generator Control Panel” is provided with the following:
zOutput Voltage Adjustment Knob
zFrequency Meter (Hz)
zAC Ammeter (Amps)
zAC Voltmeter (Volts)
zAmmeter
zVoltmeter
zVoltage Regulator
z
Open Delta Excitation System
The
There are four connections of the open delta A, B, C and D.During steady state loads, the power from the voltage regulator is supplied fromtheparallelconnectionsofAtoB,AtoD,andCtoD.Thesethree phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.
Whenaheavyload,suchasamotorstartingorashortcircuitoccurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C.This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for sensing only.No power is required from these windings.
The
Engine
InkeepingwithMQPower'spolicyofconstantlyimprovingitsproducts, the specifications quoted herein are subject to change without prior notice.
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
zThree 120/240V output receptacles
zThree auxilliary circuit breakers, @50 amps
zTwo 125 VAC output receptacles, (GFCI), 20 amps
zTwo GFCI circuit breakers @ 20amps
zFive output terminal lugs (3Ø power)
Control Box
The “Control Box” is provided with the following:
zAutomatic Voltage Regulator
zCurrent Transformer
zEmergency Relay
z
The basic controls and indicators for the
Mechanical Governor System
The mechanical governor system control the RPM of the engine. When the engine demands increase or decrease, the mechanical governor system regulates the frequency variation to within ±.5%. The electronic governor option decreases the frequency variation to within ±0.25%.
Extension Cables
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 5 ) as a guide for selecting proper extension cable size.
PAGE 20 —