DCA-45USI — GENERATOR SHUT-DOWN PROCEDURE

Normal Shut-down Procedure

To shutdown the generator, use the following procedure:

1.Switch the MAIN, AUX and GFCI circuit breakers (Figure 54) to the OFF position (no load).

Figure 54. Main, AUX. and GFCI

Circuit Breakers (OFF)

3.Let the engine cool by running it for 3-5 minutes with no load applied (circuit breakers in the OFF position).

4.Place the ignition switch (Figure 55) in the STOP position, remove the key and store in a safe place.

Figure 55. Ignition Switch (Off Position)

5.Remove all loads from the generator.

6.Allow for sufficient time for cooling and then inspect the complete unit for any damage or loosening that may have occured during operation.

7.Check the engine oil, coolant and fuel levels. Replenish as necessary.

Emergency Shut-down Procedure

1.To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 54) circuit breakers to OFF position.

2.Turn the ignition switch key to the STOP position (Figure 55).

Automatic Shut-down System

This unit is equipped with safety devices to automatically stop the engine in the event of low oil pressure (approx. 14 PSI.), or high water temperature (approx. 221° F). The alarm lamps on the Engine Control Panel (Figure 5) illuminate to signify the reason for the shut-down.

CAUTION:

After automatic shut-down, ALWAYS inspect the unit and eliminate any problems before attempting to restart. Failure to do so can damage the unit.

Before inspecting, turn the starter switch to the STOP position, place all Generator Circuit Breakers in the OFF position and allow sufficient time for adequate cooling. When ready to restart, complete all steps in the Generator Startup Procedure section of this manual.

Engine protection is furnished

NOTEduring operation, but cannot replace normal preventive maintenance.

Regularly maintain the unit as specified in the Maintenance section of this manual to prevent damage.

DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 39

Page 39
Image 39
Multiquip DCA-45US1 operation manual Normal Shut-down Procedure, Emergency Shut-down Procedure, Automatic Shut-down System