Normal Shut-down Procedure
To shutdown the generator, use the following procedure:
1. Switch the MAIN, AUX and GFCI circuit breakers
(Figure 54) to the OFF position (no load).
Figure 54. Main, AUX. and GFCI
Circuit Breakers (OFF)
Emergency Shut-down Procedure
1. To shut-down the engine in the event of an emergency,
switch the

MAIN

,
GFCI
and

LOAD

(Figure 54) circuit
breakers to OFF position.
2. Turn the ignition switch key to the STOP position
(Figure 55).
3. Let the engine cool by running it for 3-5 minutes with no
load applied (circuit breakers in the OFF position).
4. Place the ignition switch (Figure 55) in the STOP position,
remove the key and store in a safe place.
Figure 55. Ignition Switch (Off Position)
5. Remove

all

loads from the generator.
6. Allow for sufficient time for cooling and then inspect
the complete unit for any damage or loosening that
may have occured during operation.
7. Check the engine oil, coolant and fuel levels. Replenish
as necessary.
DCA-45USI — GENERATOR SHUT-DOWN PROCEDURE
Automatic Shut-down SystemWN
This unit is equipped with safety devices to automatically
stop the engine in the event of low oil pressure
(approx. 14 PSI.), or high water temperature
(approx. 221° F). The alarm lamps on the Engine Control
Panel (Figure 5) illuminate to signify the reason for the
shut-down.
Engine protection is furnished
during operation, but cannot
replace normal preventive
maintenance.
Regularly maintain the unit as specified in the Maintenance
section of this manual to prevent damage.
NOTE
CAUTION:
After automatic shut-down,
ALWAYS
inspect
the unit and eliminate any problems before
attempting to restart. Failure to do so can
damage the unit.
Before inspecting, turn the

starter switch

to the STOP
position, place all

Generator Circuit Breakers

in the OFF
position and allow sufficient time for adequate cooling. When
ready to restart, complete all steps in the Generator Startup
Procedure section of this manual.