Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure the generator is on secure level ground so it cannot slide or shift around. Also install the generator so the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to the engine and alternator parts.

CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

DCA-60SSAI — INSTALLATION

CAUTION :

An electric shock may happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from electrical shock.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 25064(b) a and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 32) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

PAGE 40 — DCA-60SSAI — PARTS AND OPERATION MANUAL— FINAL COPY (09/15/01)

Page 40
Image 40
Multiquip dca-60ssai operation manual DCA-60SSAI Installation, Outdoor Installation, Indoor Installation

dca-60ssai specifications

The Multiquip DCA-60SSAI is a portable diesel generator that stands out in the world of reliable power solutions, designed for a range of applications including construction, events, and emergency backup. With its robust build and advanced features, the DCA-60SSAI has earned a reputation for durability and efficiency.

One of the primary features of the DCA-60SSAI is its powerful 60 kVA output capacity. This generator is equipped with a high-performance, water-cooled, four-stroke diesel engine, providing not only ample power but also long-lasting operation. The unit ensures reliable performance under demanding conditions, making it suitable for heavy-duty applications.

In terms of technologies, the DCA-60SSAI incorporates a state-of-the-art digital control panel. This user-friendly interface enables operators to easily monitor voltage, frequency, and operating hours, which enhances the generator's manageability. The built-in automatic voltage regulator (AVR) maintains consistent voltage output, ensuring sensitive electronic equipment can operate safely and efficiently.

Moreover, the generator features a sound-attenuated enclosure that significantly reduces noise levels, making it more suitable for urban environments and noise-sensitive applications. This design does not only provide peace and quiet but also protects the internal components from the elements, extending the life of the generator.

When it comes to fuel efficiency, the DCA-60SSAI is optimized to consume less diesel compared to traditional generators of similar capacity. This fuel efficiency not only reduces operational costs but also decreases the frequency of refueling, which is a significant advantage for long-term projects or remote worksites.

Additionally, the DCA-60SSAI is equipped with multiple output options. This versatility makes it ideal for various applications, whether powering construction equipment, lighting, or other essential machinery on-site. Safety features like low oil pressure shutdown and emergency stop buttons ensure that the generator operates safely and that operators are protected.

In summary, the Multiquip DCA-60SSAI is a powerful, efficient, and versatile diesel generator designed to meet the demands of industrial and commercial applications. With its durability, advanced features, and user-friendly technologies, it provides reliable power solutions that users can depend on in any situation.