DCA-70USJ — GENERATOR START-UP PROCEDURE (MANUAL)

Before Starting

CAUTION - LETHAL EXHAUST HAZARD

The engine's exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WARNING - STARTINGTHE GENERATOR

NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 39) in the OFF position prior to starting the engine.

4. Close all engine enclosure doors (Figure 40).

Figure 40. Engine Enclosure Doors

5.Place the voltage selector switch in the desired voltage position (Figure 41).

Figure 41. Voltage

Selector Switch

Figure 39. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Connect the load to the receptacles or the Output Terminal Lugs as shown in Figure 13. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.

3.The output terminal lugs are protected by a plastic cover. Remove this cover to gain access to the terminals. Tighten terminal nuts securely to prevent load wires from slipping out.