GENERATOR OUTPUTS

GENERATOR OUTPUT VOLTAGES

A wide range of voltages are available to supply voltage for many different applications.Voltages are selected by using the voltage selector switch (Figure 12). To obtain some of the voltages as listed in Table 7 (see below) will require a

ne adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 12) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Figure 12. Voltage Change-Over Board

Voltage Selector Switch Locking Button

To lock the voltage selector switch, press and hold the red button located at the bottom of the switch. While holding the red button down, insert a pad lock into the hole next to the button to retain it in the inward locked position. When the lock is removed, the red button is spring loaded and will return to its normal outward unlocked position switch.

CAUTION

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the OFF position before selecting voltage.

Table 7. Voltages Available

UVWO Output

Voltage Selector Switch

Voltage Selector Switch

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/270V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Selector Switch Single-Phase 240/120V Position

 

 

 

 

 

 

 

 

Line-Neutral/

120V

N/A

N/A

240V

N/A

N/A

Line-Line

Line-Neutral

Line-Line

 

 

 

 

 

 

 

 

 

 

 

Maximum Amps

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed..

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

Voltage Selector Switch

277.8 Amps (4 wire)

1Ø 240/120 position (120V)

301A X 2 (Zigzag)

Voltage Selector Switch

138.9 Amps (4 wire)

1Ø 240/120 position (240V)

301A (Zigzag)

Voltage Selector Switch

301 Amps

3Ø 240/139 position (240V)

 

Voltage Selector Switch

150 Amps

3Ø 480/277 position (480V)

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly related to the voltage being supplied at either the output terminals or the two twist-lock auxiliary receptacles.

Tables 9 and 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the receptacles.

Table 9. GFCI Receptacle Load Capability

KW in use

Available Load Current

Twist-Lock (CS6369)

(Amps)

1Ø 240/120V

GFCI Duplex NEMA

5-20R 120V

 

72.0

0 amps per receptacle

 

 

70.8

5 amps per receptacle

69.6

10 amps per receptacle

68.4

15 amps per receptacle

67.2

20 amps per receptacle

Table 10. GFCI Receptacle Load Capability

KVA in use

Available Load Current

(UVWO Terminals)

(Amps)

3Ø 240/480V

GFCI Duplex NEMA

5-20R 120V

 

125

0 amps per receptacle

 

 

121

5 amps per receptacle

117

10 amps per receptacle

113

15 amps per receptacle

108

20 amps per receptacle

PAGE 26 — DCA125SSIU 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #3 (01/13/11)

Page 26
Image 26
Multiquip DCA125SSIU manual Generator Outputs, Generator Output Voltages

DCA125SSIU specifications

The Multiquip DCA125SSIU is a robust and versatile diesel generator that is designed to meet the power needs of various applications, from construction sites to events and emergency situations. With a power output of 125 kVA, this generator combines efficiency and reliability, making it an ideal choice for professionals who demand optimal performance in challenging environments.

One of the primary features of the DCA125SSIU is its industrial-grade a diesel engine. This engine not only delivers impressive power but also emphasizes fuel efficiency. The generator is equipped with advanced fuel management technologies that help minimize consumption while maximizing output, making it cost-effective for long-term use.

In terms of durability, the DCA125SSIU is built with a sturdy enclosure that protects it from environmental factors. The weather-resistant design ensures that it operates effectively in a variety of weather conditions, ensuring reliable performance when needed the most. Additionally, its compact size allows for easy transport and storage, which is particularly beneficial for contractors and rental companies.

The DCA125SSIU features a user-friendly control panel that provides essential information at a glance. This panel includes gauges for monitoring key parameters such as voltage, frequency, and hours of operation. It also has an automatic voltage regulator (AVR) that maintains consistent voltage output, safeguarding connected equipment from potential damage caused by power fluctuations.

Safety is a priority with the DCA125SSIU, as it is equipped with several emergency shutdown features. These include low oil pressure, high temperature, and overload protection, ensuring that the generator operates safely under all conditions. Further enhancing its operational reliability, the generator comes with a built-in fuel tank that allows for extended runtime, reducing the frequency of refueling during use.

In summary, the Multiquip DCA125SSIU is a powerful, durable, and efficient diesel generator that meets the diverse power needs of various industries. Its combination of a high-performance engine, user-friendly control panel, robust safety features, and fuel efficiency makes it an exceptional choice for anyone looking for a reliable power solution. Whether for temporary power during events, backup for critical systems, or support at construction sites, the DCA125SSIU is engineered to perform.