Multiquip DCA125SSIU manual Load Application, Single Phase Load, Three Phase Load

Models: DCA125SSIU

1 90
Download 90 pages 9.4 Kb
Page 25
Image 25

LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA125SSIU 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #3 (01/13/11) — PAGE 25

Page 25
Image 25
Multiquip DCA125SSIU manual Load Application, Single Phase Load, Three Phase Load

DCA125SSIU specifications

The Multiquip DCA125SSIU is a robust and versatile diesel generator that is designed to meet the power needs of various applications, from construction sites to events and emergency situations. With a power output of 125 kVA, this generator combines efficiency and reliability, making it an ideal choice for professionals who demand optimal performance in challenging environments.

One of the primary features of the DCA125SSIU is its industrial-grade a diesel engine. This engine not only delivers impressive power but also emphasizes fuel efficiency. The generator is equipped with advanced fuel management technologies that help minimize consumption while maximizing output, making it cost-effective for long-term use.

In terms of durability, the DCA125SSIU is built with a sturdy enclosure that protects it from environmental factors. The weather-resistant design ensures that it operates effectively in a variety of weather conditions, ensuring reliable performance when needed the most. Additionally, its compact size allows for easy transport and storage, which is particularly beneficial for contractors and rental companies.

The DCA125SSIU features a user-friendly control panel that provides essential information at a glance. This panel includes gauges for monitoring key parameters such as voltage, frequency, and hours of operation. It also has an automatic voltage regulator (AVR) that maintains consistent voltage output, safeguarding connected equipment from potential damage caused by power fluctuations.

Safety is a priority with the DCA125SSIU, as it is equipped with several emergency shutdown features. These include low oil pressure, high temperature, and overload protection, ensuring that the generator operates safely under all conditions. Further enhancing its operational reliability, the generator comes with a built-in fuel tank that allows for extended runtime, reducing the frequency of refueling during use.

In summary, the Multiquip DCA125SSIU is a powerful, durable, and efficient diesel generator that meets the diverse power needs of various industries. Its combination of a high-performance engine, user-friendly control panel, robust safety features, and fuel efficiency makes it an exceptional choice for anyone looking for a reliable power solution. Whether for temporary power during events, backup for critical systems, or support at construction sites, the DCA125SSIU is engineered to perform.