TROUBLESHOOTING (GENERATOR)

Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 19 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our company’s business offi ce or service plant.

Table 19. Generator Troubleshooting

Symptom

Possible Problem

Solution

 

AC Voltmeter defective?

Check output voltage using a voltmeter.

 

Is wiring connection loose?

Check wiring and repair.

No Voltage Output

Is AVR defective?

Replace if necessary.

 

Defective Rotating Rectifi er?

Check and replace.

 

Defective Exciter Field?

Check for approximately 17.3 ohms across J & K on CN1

 

Is engine speed correct?

Turn engine throttle lever to “High”.

Low Voltage Output

Is wiring connections loose?

Check wiring and repair.

 

Defective AVR?

Replace if necessary.

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

 

 

Short Circuit in load?

Check load and repair.

Circuit Breaker Tripped

Over current?

Confi rm load requirements and reduce.

Defective circuit breaker?

Check and replace.

 

 

Over current Relay actuated?

Confi rm load requirement and replace.