Multiquip dca25ssiu3 manual Generator Shut-Down Procedures, light tower operation, Ammeter Load

Models: dca25ssiu3

1 72
Download 72 pages 12.53 Kb
Page 34
Image 34
GENERATOR SHUT-DOWN PROCEDURES

GENERATOR SHUT-DOWN PROCEDURES

12. Place the main, GFCI, and aux. circuit breakers in the

.

ON position (Figure 48).

 

Figure 48. Main, Aux. and GFCI

Circuit Breakers (ON)

13.Observe the generator’s ammeter (Figure 49) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.

Figure 49. Ammeter (Load)

14.The generator will run until manually stopped or an abnormal condition occurs.

light tower operation

Figure 48. Main, Aux. and GFCIFigure 49. Ammeter (Load)NOTICE

For light tower operation, refer to the MLT25 Series Operation Manual (Part Number 49808).

Normal Shutdown Procedure

light tower operation WARNING

NEVER stop the engine suddenly except in an emergency.

To shutdown the generator, use the following procedure:

1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 50 to the OFF position.

Figure 50. Main, GFCI and Load

Circuit Breakers Off

2.Let the engine cool by running it at low speed for 3-5 minutes with no load applied.

3.Place the ignition switch (Figure 51) in the “STOP” position, remove the key and store in a safe place.

Figure 51. Ignition Switch (Stop Position)

4.Remove all loads from the generator.

5.Inspect entire generator for any damage or loosening of components that may have occurred during operation.

Emergency Shutdown Procedure

1.Turn ignition switch key to the STOP position.

2.To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 50) circuit breakers to OFF position.

Automatic Shut-down System

This unit is equipped with safety devices to automatically stop the engine in the event of low oil pressure, approximately 14 psi (97 kPa), or high water temperature, approximately 230° F (110° C). The alarm lamps on the Engine Control Panel illuminate to signify the reason for the shutdown.

Normal Shutdown ProcedureNOTICE

Before inspecting, turn the ignition switch to the STOP position, place all circuit breakers in the OFF position and allow sufficient time for adequate cooling. When ready to restart, complete all steps in the Generator Startup Procedure section of this manual.

page 34 — DCA25SSIU3 (with MLT25 series) • operation and parts manual — rev. #1 (01/24/13)

Page 34
Image 34
Multiquip dca25ssiu3 manual Generator Shut-Down Procedures, light tower operation, Normal Shutdown Procedure, Ammeter Load