Multiquip GAC-6HZR operation, Before Starting the Engine, Main Circuit Breaker OFF, Choke Lever

Models: GAC-6HZR

1 82
Download 82 pages 20.5 Kb
Page 21
Image 21
operation

operation

This section is intended to assist the operator with the initial start-up of the portable generator. It is extremely important that this section be read carefully before attempting to use the generator in the field.

Before Starting the Engine

1.Be sure to disconnect all electrical loads from the generator prior to starting the engine.

2.NEVER start the engine with the main circuit breaker in the ON position. Always place circuit breaker (Figure 9) in the OFF position before starting.

Figure 9. Main Circuit Breaker (OFF)

3.NEVER start the engine with the GFCI circuit breaker in the ON position. Always place GFCI circuit breaker (Figure 10) in the OFF position before starting.

Figure 10. GFCI Circuit Breaker (OFF)

Starting the Engine

1.Place the engine fuel valve lever (Figure 11) in the ON position.

Figure 11. Engine Fuel Valve Lever (ON)

2.Place the choke lever (Figure 12) in the CLOSED position if starting a cold engine.

Figure 12. Choke Lever

3.Place the choke lever (Figure 12) in the OPEN position if starting a warm engine or the temperature is warm.

4.Place the generator's operation switch (Figure 13) in the ON position.

Figure 13. Operation Switch (ON)

5.Grasp the starter grip (Figure 14) and slowly pull it out. The resistance becomes the hardest at a certain position, corresponding to the compression point. Pull the starter grip briskly and smoothly for starting.

Figure 14. Starter Grip

Before Starting the Engine NOTICE

DO NOT pull the starter rope all the way to the end.

DO NOT release the starter rope after pulling. Allow it to rewind as soon as possible..

GAC6HZR 60 hz GENERATOR • operation and parts manual — rev. #1 (03/31/10) — page 21