DCA-70SSIU (60 Hz) — OUTPUT TERMINAL PANEL FAMILIARIZATION

DCA-70SSIU (60 Hz) — OUTPUT TERMINAL PANEL FAMILIARIZATION

120VAC GFCI Receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any voltage selector switch position. Each receptacle is protected by a 20 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the U, V, and W output terminal lugs.

Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the Test Button (See Figure 9) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.

Figure 9. G.F.C.I. Receptacle

Twist Lock Dual Voltage 120/240 VAC Receptacles

There are three 120/240V, 50 amp auxilliary twist-lock (CS-6369) recepacles (Figure 10) provided on the output terminal panel.These receptacles can only be accessed when the voltage selector switch is placed in the single- phase 240/120 position.

Each auxilliary receptacle is protected by a 50 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the Output Terminal Lugs.

Turn the voltage regulator control knob (Figure 11) on the control panel to obtain the desired voltage.Turning the knob clockwise will increase the voltage, turning the knob counter- clockwise will decrease the voltage.

Figure 11.Voltage Regulator Control Knob

Removing the Plastic Face Plate (HardWire Hookup Panel)

The Output Terminal Lugs are protected by a plastic face plate cover (Figure 12). Un-screw the securing bolts and lift the plastic terminal cover to gain access to the terminal enclosure.

After the load wires have been securely attached to the terminal lugs, reinstall the plastic face plate.

Figure 12. Plastic Face Plate (Output Terminal Lugs)

Figure 10. 120/240V Twist-Lock

Auxiliary Receptacles

DCA-70SSIU (60 Hz) — OPERATION AND PARTS MANUAL — REV. #1 (01/06/09) — PAGE 25