troubleshooting (controller)
CAUTION
Before opening the enclosure to perform troubleshooting or any service task, isolate the controller from any possible source of power. Failure to do so may result in serious personal injury or death due to electrical shock.
Troubleshooting (MEC20 Controller)
Symptom | Possible Problem | Solution | |
Does not power up even |
| Check wiring and repair. NOTE: The MEC 20 electronic | |
| fuse triggers when there is an overload condition and does | ||
with correct DC power | Wiring errors or short circuit? | ||
not reset until the supply voltage is removed and overload | |||
applied |
| ||
| condition is corrected. | ||
|
| ||
|
|
| |
|
| Check that the "watchdog" LED on the rear of the PCB is | |
| Microprocessor defective? | flashing red meaning that the microprocessor is working. If | |
|
| not, repair or replace microprocessor. | |
LCD is not operational | Insufficient DC supply voltage? | Check voltage at input terminals B+ and B- | |
|
| Adjust LCD contrast potentiometer (R115) on the rear of | |
| Bad LCD resolution? | PCB for good pixel resolution for the operating temperature | |
|
| of the unit. | |
| Controller not in OFF mode? | Check that the controller is set to the OFF mode before | |
Controller cannot be | resetting. | ||
| |||
"reset" | Engine is running? | Check that the engine has come to a complete stop before | |
| resetting. | ||
|
| ||
| Shutdown circuits reset? | Check that all shutdown circuits are reset (red shutdown | |
| LED must be off). | ||
|
| ||
|
| Engine speed signal must be detected (speed signal green | |
No "RUN" output signal | No engine speed signal? | LED on) during cranking if the | |
is enabled. Verify correct magnetic | |||
| |||
|
| (2.0 VAC min.) | |
|
| Check that the RUN output LED (on the rear of the PCB) is | |
| RUN output LED off? | on. If yes, verify relay contact operation on terminals #18 and | |
|
| #19. | |
Overspeed shutdown occurs |
| Verify that the controller has been programmed with the correct | |
Controller not correctly programmed? | values for the number of flywheel teeth, nominal RPM, and | ||
at normal speed |
| overspeed setpoint percentage. | |
|
| ||
|
| Verify that the controller has been programmed with the correct | |
| Controller not correctly programmed? | values for voltage sensing PT ratio and/or current sensing CT | |
|
| ratio. | |
| Battery not properly grounded? | Verify that the battery supply DC negative conductor is properly | |
| grounded to the engine block (i.e. to a common ground point.) | ||
Voltage or current metering |
| ||
| Verify that the controller's analog input has been properly | ||
is reading incorrectly | Analog input not properly calibrated? | ||
calibrated. | |||
| |||
|
| Verify that the voltage sensing wiring connection to the | |
| Incorrect wiring? | controller matches power distribution type (Note: standard | |
| direct voltage connection requires that the generator's neutral | ||
|
| ||
|
| is solidly grounded). |