6
PEDESTAL MODELS OUTSIDE AIR
If possible connect the air intake at the pedestal’s back or bottom to the outside with a 4 inch (100mm) diameter fresh air kit available at your Napoleon/Wolf Steel Ltd. dealer. Follow detailed instructions under “Mobile Home Outside Air”.
| B" | |
BASE | 4. | |
PEDESTAL | 5" | |
BELOW | ||
| ||
| AREA | |
FLOOR | ||
A (in.) | B(in.) |
STOVE
| 1100 | 8 5/8" | 9 3/4" | |
FIGURE 7 | 1400 | 11 1/8" | 9 3/4" | |
1900 | 14 7/8" | 9 3/4" | ||
|
| WALL | |
| If possible, design the installa- |
|
| tion so that the connector does |
|
DO NOT USE ANY MAKESHIFT MATERIALS DUR- | not pass through a combustible |
|
ING INSTALLATION. | wall. If during your installation you |
|
1. Move the stove into position with the flue centered, mid- | must pass through a combustible |
|
point between two joists to prevent having to cut them. Use | wall, check with your building |
|
a plumb bob to line up the centre. | inspector before you begin. Also |
|
2. Cut and frame an opening in the roof to provide a 2” | check with the chimney connec- | This is the preferred |
clearance between the outside of the chimney and any | tor manufacturer for any specific | method of passing a |
flue pipe through a | ||
combustible material. | requirements. | combustible wall to a |
DO NOT FILL THIS SPACE WITH ANY TYPE OF | Consult with your dealer regarding | FIGURE 8 masonry chimney. |
MATERIAL. | special connection components |
|
Nail headers between the joist for extra support. Firestop | available for use for wall | |
spacers must be placed on the bottom of each framed opening | Use only parts that have been tested and listed for use in a | |
in any floor or ceiling that the chimney passes through. | wall |
|
3. Hold a plumb bob from the underside of the roof to deter- | MOBILE HOME | |
mine where the opening in the roof should be. Cut and frame |
the roof opening to maintain proper 2” clearances.
A
HEADERS A
FIRESTOP SPACER -
UNDERSIDE OF JOIST
FIGURE 5
ADDING CHIMNEY SECTIONS
Add chimney sections, according to the manufacturers installation in-
structions, securely, to the required height. The chimney must extend, at least, 3 feet above its point of contact with the roof and at least
2 feet higher than any wall, roof or building within 10 feet. FIGURE 6.
If your chimney system is enclosed within the attic area, a rafter radiation shield is required.
BACK WALLBACK WALL
6" |
| WALL | 45 ° | WALL |
| 10" | 2" | ||
| SIDE | SIDE | ||
|
|
| ||
FIGURE 9 |
|
| FIGURE 10 |
|
The pedestal base must be firmly bolted to the floor with 1/4 inch lag bolts. Minimum clearances to combustibles are as shown in FIGURE 9.
VENTING
Connect the stove to a chimney system using a listed double wall connector. Use a chimney system listed to ULC S629 in Canada or UL103HT in the U.S.A.
The chimney must be installed in accordance with the manu- facturer’s instructions. Use only specified components with no substitutions. The chimney and pipe must extend at least 8 feet above the stove and 3 feet above the highest point of the roof. Install a rain cap at the top which will not impede the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight does not rest on the stove.