TROUBLE SHOOTING GUIDE
BEFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED.
SYMPTOM | PROBLEM | TEST SOLUTION |
|
|
|
|
|
|
Pilot goes out when the gas knob is re- leased.
The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermo- couple has cooled. Allow approximately 60 seconds for the thermocouple to cool.
System is not correctly purged. | - | purge the gas line with the glass door open. | |
|
|
|
|
Out of propane gas. | - | fill the tank. | |
|
|
|
|
Pilot flame is not large enough | - | turn up the pilot flame. | |
|
|
| |
Pilot flame is not engulfing the | - | gently twist the pilot head to improve the flame pattern | |
thermocouple. | around the thermocouple. | ||
|
|
| |
Thermocouple shorting / faulty. | - | loosen and tighten thermocouple. | |
| - | clean thermocouple and valve connection. | |
| - | replace thermocouple. | |
| - | replace valve. | |
|
|
| |
Faulty valve. | - | replace. |
Pilot will not light. | No spark at pilot burner | - | check if pilot can be lit by a match |
|
| - | check that the wire is connected to the push button ignitor. |
|
| - | check if the push button ignitor needs tightening. |
|
| - | replace the wire if the wire insulation is broken or frayed. |
|
| - | replace electrode if ceramic insulator is cracked or broken. |
|
| - | replace the push button ignitor. |
|
|
|
|
| Out of propane gas | - | fill the tank. |
| Spark gap is incorrect | - | spark gap should be 0.150" to 0.175" (5/32" to 11/64" |
|
| approx.) from the electrode tip and the pilot burner. To en- | |
|
| sure proper electrode location, tighten securing nut (finger | |
|
| tight plus 1/4 turn). | |
| No gas at the pilot burner | - | check that the manual valve is turned on. |
|
| - | check the pilot orifice for blockage. |
|
| - | replace the valve. |
|
| - | call the gas distributor. |
|
|
|
|
Pilot burning; no gas | Themostat or switch is defective. | - | connect a jumper wire across the wall switch terminals; if |
to main burner; gas |
| main burner lights, replace switch / thermostat. | |
knob is on 'HI'; wall | Wall switch wiring is defective. | - disconnect the switch wires & connect a jumper wire across | |
switch / thermostat is | terminals 1 & 3; if the main burner lights, check the wires for | ||
on. |
| defects and / or replace wires. | |
|
|
|
|
| Main burner orifice is plugged. | - | remove stoppage in orifice. |
| Faulty valve. | - | replace. |
|
|
|
|
Pilot goes out while | Gas piping is undersized. | - | turn on all gas appliances and see if pilot flame flutters, |
standing; Main burner |
| diminishes or extinguishes, especially when main burner | |
is in 'OFF' position. |
| ignites. Monitor appliance supply working pressure. | |
|
| - | check if supply piping size is to code. Correct all under- |
|
| sized piping. | |
|
|
|
|
Main burner goes out; | Pilot flame is not large enough or | - | turn up pilot flame. |
pilot stays on. | not engulfing the thermopile | - replace pilot assembly. | |
| Thermopile shorting | - clean thermopile connection to the valve. Reconnect. | |
|
| - replace thermopile / valve. | |
| Remote wall switch wire is too | - | shorten wire to correct length or wire gauge. |
| long; too much resistance in the |
|
|
| system. |
|
|
|
|
|
|
| Faulty thermostat or switch. | - | replace. |
|
|
|
|