Napoleon Fireplaces GE38PT-M, GE38NT-M Using Rigid Vent Components, Fireplace Vent Connection

Models: GE38PT-M GE38NT-M

1 28
Download 28 pages 63.44 Kb
Page 14
Image 14
FIREPLACE VENT CONNECTION

14

Do not nail through

 

the lower portion of the

 

flashing.

Make

 

weather-tight by seal-

 

ing

with

caulking.

 

Where possible, cover

 

the

sides

and top

 

edges of the flashing

 

with roofing material.

FIGURE 23

6.Apply a heavy bead of weatherproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved. Attach the other storm collar centered between the air intake and the air exhaust slots onto the air termi- nal. Tighten securely. FIGURE 23. Attach the vertical rain cap.

Spacers are attached to the 4" inner flex liner at prede- termined intervals to maintain a 1-1/4" air gap to the 8" outer liner. These spacers must not be removed.

7.If more liner needs to be used to reach the fireplace, follow the same procedure as found in EXTENDED HORI- ZONTAL AIR TERMINAL INSTALLATION. The vent system must be supported approximately every 3 feet for both ver- tical and horizontal runs. Use Wolf Steel support ring as- sembly or equivalent noncombustible strapping to main- tain a clearance to combustibles.

FIREPLACE VENT CONNECTION

1.Install the 4 inch diameter aluminium flexible liner to the fireplace. Secure with 3 screws and flat washers. Seal the joint and screw holes using the high temperature seal- ant provided. FIGURE 24.

2.Install the 7 inch diameter aluminium flexible liner to the fireplace. Attach and seal the joints.

FIGURE 24

USING RIGID VENT COMPONENTS

The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Wolf Steel vent spacers every 3 feet and either side of each elbow to maintain the minimum 1¼" clearance between the outer and inner vent pipes. Use Wolf Steel support ring assem- bly or equivalent noncombustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs.

3.Holding the air terminal (with the air deflectors to the top), insert into both vent pipes with a twisting motion to ensure that both the terminal sleeves engage into the vent pipes and sealant. Secure the terminal to the exterior wall and make weather tight by sealing with caulking (not supplied).

The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return flange.

 

 

EXTENDED HORIZONTAL AND CORNER

HORIZONTAL AIR TERMINAL INSTALLATION

 

 

AIR TERMINAL INSTALLATION

 

 

 

 

 

FIGURE 25

1.Move the fireplace into position. Meas-

ure the vent length required between terminal

and fireplace taking into account the additional length needed for the finished wall surface and any 1¼" overlaps between venting components.

2.Apply high temperature sealant to the outer edge of the 4" inner collar of the fireplace. Attach the first vent component and secure using 3 self tapping screws. Repeat using 7" piping.

1.Follow the instructions for "Horizontal Air Terminal In- stallations", items 1 to 3.

2.Continue adding components alternating inner and outer venting. Ensure that all 4" venting and elbows have sufficient vent spacers attached and each component is securely fastened to the one prior. Attach the 4" telescopic sleeve to the vent run.

Repeat using a 7" tel-

 

escopic sleeve. Secure

 

and seal as before. To

 

facilitate completion, at-

 

tach 5" and 8" couplers

FIGURE 26

to the air terminal.

 

3.Install the air terminal. See item 3 of the Horizontal Air Terminal Installation. Extend the 4" telescopic sleeve; connect to the air terminal assembly. Fasten with self tapping screws and seal. Repeat using the 7" telescopic sleeve.

W415-0429 / C / 11.04.05

Page 14
Image 14
Napoleon Fireplaces GE38PT-M manual Using Rigid Vent Components, Fireplace Vent Connection, Extended Horizontal And Corner