16
OPTIONAL BLOWER INSTALLATION
!WARNING
INSTALLATION TO BE DONE BY A QUALIFIED INSTALLER and must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States.
FIGURE 32
1.Turn off any electrical power to the fi replace (if applicable). Open the lower louvred control door.
2.Locate the vibration reducing pad over the two threaded studs, piercing 2 holes into the pad. The fan must be installed on the left hand side of the fi replace entirely on the pad.
3.Slide the fan to the back of the fi replace taking care not to damage the terminals. Position the fan onto the studs and secure using the lock washers and wing nuts provided. Pull the leads to the front and right side of the ashpan housing.
4.Remove the junction box. Use a nut connector to attach the black wires of the variable speed switch and the power.
5.Pass the two fan leads and one thermodisc lead through the junction box bushing. The thermodisc is located inside the outer shell, just above the louvre door. Connect one fan lead to the thermodisc lead and the other fan lead to the white wire of the variable speed switch using nut connectors.
6.Thread the other thermodisc lead through the junction box bushing and connect to the white wire of the power cord using a nut connector. Secure ground wire (green) to the threaded weld stud located on the junction box wall. Reposition the junction box. Verify that the wires will not interfere with the fan.
BECAUSE THE BLOWER IS THERMALLY ACTIVATED, WHEN TURNED ON, IT WILL AUTOMATICALLY START APPROXIMATELY
Drywall dust will penetrate into the blower bearings causing irreparable damage and must be prevented from coming into contact with the blower or its compartment. Any damage resulting from this condition is not covered by the warranty policy.
FIGURE 33
BLOWER |
|
| |
WING NUT & | VIBRATION | THERMODISC | |
LOCK WASHER | |||
REDUCING PAD | |||
| |||
|
| ||
|
| VARIABLE | |
|
| SPEED | |
FAN |
| SWITCH | |
|
| JUNCTION BOX |
FEATURES
CONTROLLING COMBUSTION AIR
!WARNING
Fireplace operation does require air. Do not take air from other fuel burning appliances which can result in improper venting (smoking) or air dilution. Always provide adequate makeup air.
If the outside combustion air kit is not used, air may still be drawn directly into the fi replace through the lower louvres. Outside and inside air may be combined by pulling the outside air lever out as far as possible, and turning the lever 90° to its locking position.
Should you fi nd a frost build up on | the air control box or a draft |
from the fireplace, close the outside | air lever when the fi replace |
is not in use. |
|
Air control box is shipped with inside a i r c o v e r plate in open position.
FIGURE 34
ACHIEVING PROPER DRAFT
Draft is the force which moves air from the fi replace up through the chimney. The amount of draft in your chimney depends on the length of the chimney, local geography, nearby obstructions and other forces. Adjusting the draft control regulates the temperature. The draft can be adjusted from a low burn rate with the handle at the bottom setting to a fast burn rate with the handle at the top setting. Inadequate draft may cause
open).
FIGURE 35
NorthlineExpress.com | http://www.northlineexpress.com |