Appendix A Specifications for NI2503
©
National Instruments Corporation A-5 NI 2501/2503 User Manual
NI 2503

Input Characteristics

Number of Relays Available
as Channels............................................ 24
Common Mode Voltage
Channel to Channel.........................30 Vrms/60 VDC
Channel to Earth............................. 30 Vrms/60 VDC
Maximum Allowed Voltage—Differential Mode or Single ended
AC...................................................30 Vrms
DC...................................................60 VDC
Maximum Switching Capacity—Differential Mode or Single ended
DC...................................................1 A @ 30 VDC
Maximum Switching Power per
Differential Channel or Single ended.....60 VA, 30 W
Contact on Resistance (Initial)...............100 m
Contact Material.....................................Gold-clad Silver Alloy

Transfer Characteristics

Thermal E.M.F. (Differential)................<2 µV
Maximum Frequency Bandwidth 50 Ω Termination
Worst case channel......................... 35 MHz