How to Purge Air Tubes:

Installation instructions Notes

How to Purge Air Tubes:

(1). Unscrew and remove caps from 2 and 3-way valves.

(2). Unscrew and remove cap from service valve.

(3). Connect vacuum pump flexible hose to the service valve.

(4). Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.

(5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop vacuum pump.

(6). Open 2-way valve 1/4 turn then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.

(7). Turn 2 and 3-way valves stem to fully the valves. Disconnect vacuum pump flexible hose.

(8). Replace and tighten all valve caps.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundNotesManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Manual background Please read this manual before installing and using it.

Manual background Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.

Manual background Testing run the air conditioner after finishing installation, and record details of operation. Manual background Type of fuse used on indoor unit controller is 50T, with rating 3.15A,AC250V. .

Manual background The fuse for the whole unit is to be provided by the user according to the current at maximum power Input or use other over-current protective device instead.

Manual background Only the air conditioner can be connected to the power line.

Manual background The power connection for the air conditioner has to be done at the main power distribution which has to be of a low impedance.

Manual background In order to ensure the suitability of the equipment for connection, the user should consult with the supply authority, if necessary, that the service current capacity at the interface point is sufficient for the equipment.

Manual background Refer to the rating plate of the equipment for power consumption details.

Manual background If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or similarly qualified person in order to avoid a hazard.