New Media Technology 9212 manual Pro Hardware connection recommend, Slink mode Resistance Input

Models: 9212

1 26
Download 26 pages 9.22 Kb
Page 10
Image 10
Source mode ( Voltage input) :

IP POWER 9212 USER MANUAL

Source mode ( Voltage input) :

IN1-IN4 contacts are active signal sensor. If the voltage difference between the two contacts in one set within 0V~3V, 9212 shows ON. It the voltage difference within 4V~24V, 9212 shows OFF. So user can detect the change of equipment. Such as smoke detector, light detector and gas detector.

NOTE:

1. The data in this figure is the average measure value. To ensure the correct detection, we suggest user set the voltage lower than 3V when it shows OFF and higher than 4V when it shows ON

2. The maximum measure voltage is 24V.

.

Slink mode (Resistance Input ) :

IN5-IN8 contacts are short circuit sensor. If the resistance between the two contacts in one set within

0Ω~200Ω, 9212 shows ON. If the resistance within 500Ω~∞, 9212 shows OFF. So user can detect the movement of equipment through the magnetic reed switch or other kind of reactive sensors.

NOTE:

1. The data in this figure is the average measure value. To ensure the correct detection, we suggest user set the voltage lower than 200Ω when it shows ON and higher than 500Ω when it shows OFF.

2. When measure the resistance of web contacts, the maximum voltage is 5V and the maximum currency is no more than 10mA

PS: magnetic reed switch: using the magnetic field of the magnet to produce a signal when there is a movement happened in switch. Low cost and easy to use is the chief characteristic of magnetic reed switch. Most of them are used in security equipment, living product and automatic mechanism.

9202 Pro Hardware connection (recommend)

IP Power 9202 Pro offers 4 sets of NC(Normal Close ) – Out 1Out 4 4 sets of NO (Normal Open ) –Out 5Out 8.

Maximum Rated Voltage: 240V/AC, 60V/DC

Maximum Rated Currency: 12A AC/DC

Maximum Switch time: Max 10ms

Environment Temperature: -30°C~ + 55°C

NOTICE: Only the professionals should operate the following operations in this section and the common user DO NOT try it!

For example—Light ball

1 Use the electrical wire of the equipment

- 9 -

VER. X.X,

Page 10
Image 10
New Media Technology 9212 manual Pro Hardware connection recommend, Slink mode Resistance Input, Source mode Voltage input