Device type

Type

Condition

Panel response

Analogue Value

Status bits

Output bits

Default cause

Comments

 

Code

 

 

 

(210)

 

 

and effect

 

Series 90 optical

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

smoke

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 optical

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

smoke

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 beam

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

Detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 flame

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 multi-

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

sensor opt/heat

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

detector

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

Series 90 heat

6

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 heat

6

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector standard

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

Document Ref: Nex8inst.doc/Rev0 09.07.00

Page 29 of 30

Originator MC Checked by AC__

Page 29
Image 29
Nexus 21 A1557 technical specifications Is in fire Fault Data fault AV = 0 to