Nexus 21 A1557 technical specifications Is in fire Fault Data fault AV = 0 to

Models: A1557

1 30
Download 30 pages 61.44 Kb
Page 29
Image 29

Device type

Type

Condition

Panel response

Analogue Value

Status bits

Output bits

Default cause

Comments

 

Code

 

 

 

(210)

 

 

and effect

 

Series 90 optical

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

smoke

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 optical

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

smoke

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 beam

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

Detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 flame

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 multi-

5

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

sensor opt/heat

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

detector

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

Series 90 heat

6

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

XP95 heat

6

Quiescent

None

AV = 8 to 44

Echo

0

= remote LED

Bit 0 and bit 2

See note 1.

detector standard

 

Fire

Fire

AV = 55 to 127

output bits

1

= self test

set when device

 

 

 

Alert

Alert

AV = 45 to 54

 

2

= LED

is in fire

 

 

 

Fault

Data fault

AV = 0 to 7

 

 

 

 

 

Document Ref: Nex8inst.doc/Rev0 09.07.00

Page 29 of 30

Originator MC Checked by AC__

Page 29
Image 29
Nexus 21 A1557 technical specifications Is in fire Fault Data fault AV = 0 to