Getting Started

Figure 5: Changing a keypad/display menu item

Table 7: Keypad/display menu item list

Display

Keypad menu item list

Abr.

Description

RO

05

Default

RW1

 

 

 

 

 

 

 

rA

Reset Alarm Input

 

Enter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable

RW

x

//2

 

 

 

the alarm again, enter 0.

 

 

 

HC

UVC (Heat/Cool) Mode

UVCM

Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.

RO

x

 

Output

Heat, 9 = Fan Only

 

 

UVC State Output

 

Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 =

 

 

 

St

 

UVCS

Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11

RO

x

 

 

 

 

= Heat Mode Cant Heat, 12 = CantCool, 13 = Emerg Heat Mode Cant Heat, 14 =

 

 

 

 

 

 

Heat Mode Low Limit, 15 = Cool Mode Low Limit

 

 

 

d0

Discharge Air Temp Set

DATS

Display current DA temperature set point.

RO

x

 

point Output

 

d1

OutputDischarge Air Temp

DAT

Display current DA temperature.

RO

x

 

d2

Ventilation Cooling Low

VCLL

Adjust economizer cooling DA temperature low limit.

RW

x

54°F

Limit set point

(12°C)

d3

Mechanical Cooling Low

MCLL

Adjust mechanical cooling DA temperature low limit.

RW

x

45°F

Limit set point

(7°C)

SL

Slave Type Configuration

 

Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave

 

 

 

 

 

follows master). This feature requires a network over which the master and slave

RW

x

0

 

 

 

UVCs can communicate.

 

 

 

Eo

OutputEffective Occupancy

 

Display current occupancy.

RO

x

 

o(

Occupancy Override

 

Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting

 

 

//2

Input

 

this variable is intended only for troubleshooting. Once you are done, cycle unit

RW

x

 

 

 

power to clear this variable and return the UVC to normal operation.

 

 

 

(o

Occupied Cooling set

OCS

Adjust occupied cooling set point.

RW

x

73.4°F

point

(23°C)

(S

Standby Cooling Set

SCS

Adjust standby cooling set point.

RW

x

77°F

point

(25°C)

(U

Unoccupied Cooling Set

UCS

Adjust unoccupied cooling set point.

RW

x

82.4°F

point

(28°C)

ko

Occupied Heating Set

OHS

Adjust occupied heating set point.

RW

x

69.8°F

point

(21°C)

kS

Standby Heating Set

SHS

Adjust standby heating set point.

RW

x

66.2°F

point

(19°C)

kU

Unoccupied Heating Set

UHS

Adjust unoccupied heating set point.

RW

x

60.8°F

point

(16°C)

rS

Wall Sensor Type

 

Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F.

RW

x

0

o1

Outside Air Damper

OADP

Display OA damper position.

RO

x

 

Position Output

 

o2

OAD Min Position High-

OADH

Adjust OA damper minimum position with IAF at high speed. (This variable is

RW

x

20%

Speed Set point

factory set to 5% open when the unit is ordered with optional CO DCV.)

 

 

 

2

 

 

 

o3

OAD Min Position Med-

 

Adjust OA damper minimum position with IAF at medium speed. (This variable is

 

 

 

Speed Set point

OADM

not used when the optional CO2 DCV is enabled. Only OADH is active as the OA

RW

x

25%

 

 

 

damper minimum regardless of fan speed.)

 

 

 

o4

OAD Min Position Low-

 

Adjust OA damper minimum position with IAF at low speed. (This variable is not

 

 

 

Speed Set point

OADL

used when the optional CO2 DCV is enabled. Only OADH is active as the OA

RW

x

30%

 

 

 

damper minimum regardless of fan speed.)

 

 

 

10

McQuay OM 751

Page 10
Image 10