Description of Operation
Exhaust Fan ON/OFF Signal
This relay output provides one set of Normally Open dry contacts that can be used to signal the operation of an exhaust fan. When the OA damper opens more than the Energize Exhaust Fan OA Damper set point, then the relay output signals the exhaust fan ON (contacts closed). When the OA damper closes below this set point, the relay output signals the exhaust fan OFF (contacts open).
Auxiliary Heat Signal
This relay output provides one set of Normally Open dry contacts that can be used to operate an auxiliary heat device. The UVC by default is configured to operate a Normally Open auxiliary heat device
Table 20: Auxiliary heat start/stop calculation
Start/Stop | Calculation |
Auxiliary heat | Primary Heat |
starts when: | more than two minutes |
| AND |
| EffectiveSpaceTemp ≤ EffectiveSetpoint – |
| AuxiliaryHeatStartDifferential |
Auxiliary heat | EffectiveSpaceTemp ≥ (EffectiveSetpoint – |
stops when: | AuxiliaryHeatStartDifferential) + |
| AuxiliaryHeatStopDifferential |
McQuay OM 751 | 39 |