Diagnostics and Service
Space Humidity Sensor Failure (optional) (FA)
The Space Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
•IA/OA Enthalpy comparison economizer (if used) is disabled.
•Dehumidification function (optional) is disabled.
•Fault is indicated.
Outdoor Humidity Sensor Failure (optional) (Fb)
The Outdoor Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
•IA/OA Enthalpy comparison or OA Enthalpy economizer (if used) is disabled.
•Fault is indicated.
Space CO2 Sensor Failure (optional) (FC)
The Space CO2 Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
•CO2 Demand Controlled Ventilation function is disabled.
•Fault is indicated.
Change Filter Indication (FF)
The Change Filter Indication fault occurs when the UVC calculates that the total fan run time has exceeded the allowed number of hours since the last filter change.
Effect:
•Fault is indicated.
EPROM Memory Indicator (EE)
The EPROM Memory Indicator occurs when an unusual electrical event has scrambled the EPROM memory within the controller board. In the event that this happens, the controller board must be replaced.
Configuration Display (--)
The Configuration Display occurs when the display file “**.cfg” is incorrect or has not been downloaded with the appropriate file from service tools.
Troubleshooting Temperature Sensors
The UVC is configured to use passive positive temperature coefficient (PTC) sensor whose resistance increases with increasing temperature. The element has a reference resistance of 1035 ohms at 77°F (25°C). Each element is calibrated according to the tables shown.
Use the following procedure to troubleshoot a suspect sensor.
1Disconnect both sensor leads from the UVC.
2Using some other calibrated temperature sensing device, take a temperature reading at the sensor location.
44 | McQuay OM 751 |