Table 19: How economizer enable/disable tests are selected
Table 18: Economizer enable/disable tests defined
Temperature Comparison with Enthalpy Comparison requires both an optional OA humidity sensor and an optional IA humidity sensor.
Note –
Temperature Comparison with Enthalpy Comparison Economizer (optional)
If the optional Leading Edge economizer function is selected, the unit ventilator is provided from the factory with both the IA humidity and OA humidity sensors, which are used along with the IA temperature and OA temperature sensors to calculate IA enthalpy and OA enthalpy. In this case, the UVC is factory set for Economizer Strategy 2 and uses the Temperature Comparison with Enthalpy Comparison Economizer function.
Note –
Temperature Comparison with OA Enthalpy Setpoint Economizer requires an optional OA humidity sensor.
Description of Operation
Expanded (optional)—Temperature Comparison with OA Enthalpy Setpoint Economizer (Strategy 1)
Leading Edge (optional)—Temperature Comparison with Enthalpy Comparison Economizer (Strategy 2)
Temperature Comparison Economizer (default)
If the default Basic economizer function is selected, the unit ventilator is provided from the factory without the optional IA and OA humidity sensors. In this case, the UVC is factory set for Economizer Strategy 1—the UVC automatically detects that no OA humidity sensor is present and adjusts to use the Temperature Comparison Economizer function.
Temperature Comparison with OA Enthalpy Setpoint Economizer (optional)
If the optional Expanded economizer function is selected, the unit ventilator is provided from the factory with the optional OA humidity sensor, which is used along with the OA temperature sensor to calculate OA enthalpy. In this case, the UVC is factory set for Economizer Strategy 1 and uses the Temperature Comparison with OA Enthalpy Setpoint Economizer function.

Tests

Economizer

Enable test

Disable test

enable/disable tests

A

OA temp set point

EffectiveOATemp < (EconOATempSetpt – EconTempDiff)

EffectiveOATemp >= EconOATempSetpt

B

IA/OA differential temp

EffectiveOATemp < (EffectiveSpaceTemp – 3.6°F – EconTempDiff)

EffectiveOATemp >= (EffectiveSpaceTemp – 3.6°F)

C

OA enthalpy set point

EffectiveOAEnthalpy < (EconOAEnthalpySetpt –

EffectiveOAEnthalpy >= EconOAEnthalpySetpt

EconEnthalpyDiff)

 

 

 

D

IA/OA differential

EffectiveOAEnthalpy < (EffectiveSpaceEnthalpy –

EffectiveOAEnthalpy >= EffectiveSpaceEnthalpy

enthalpy

EconEnthalpyDiff)

 

 

Economizer

Space temp sensor

OA temp sensor

Space humidity

OA humidity sensor

Economizer enable/

strategy

sensor

disable tests

 

 

 

All

Unreliable

Don’t care

Don’t care

Don’t care

OA damper closed

Don’t care

Unreliable

Don’t care

Don’t care

OA damper closed

 

Basic

Reliable

Reliable

Don’t care

Unreliable

Test B

Reliable

Reliable

Don’t care

Reliable

Test C

 

Expanded

Reliable

Reliable

Don’t care

Reliable

Test C and Either

Test B or Test A

 

 

 

 

 

 

Reliable

Reliable

Reliable

Reliable

Test D and Test B

Leading Edge

Reliable

Reliable

Unreliable

Reliable

Test B

Reliable

Reliable

Reliable

Unreliable

Test B

 

 

Reliable

Reliable

Unreliable

Unreliable

Test B

 

Note:

The hard-wired sensor and the equivalent input must both be unreliable for the value to be considered

 

 

unreliable.

 

 

 