American Standard UV05 manual Remote Wall-MountedSensor with +/-3F, Adjustment optional

Models: UV05

1 50
Download 50 pages 38.18 Kb
Page 27
Image 27
Remote Wall-Mounted Sensor with +/–3°F

Description of Operation

Remote Wall-Mounted Sensor with +/–3°F

Adjustment (optional)

When the optional remote wall-mounted sensor with +/–3°F adjustment dial is used, the UVC effectively writes the value of the set point adjustment dial to the Set Point Offset Input variable.

Note – If a network connection is used to adjust the Set Point Offset Input variable, you must not use the optional remote wall-mounted sensor with +/–3°F adjustment.

If the keypad/display is used by room occupants to adjust the Set Point Offset, do not use the optional remote wall-mounted sensor with +/–3°F adjustment.

If you have the optional remote wall-mounted sensor with +/–3°F adjustment and an occupant uses the keypad to make Set Point Offset adjustments, this overrides any +/–3°F adjustment on the optional remote wall-mounted sensor since the keypad/display has higher priority. If you find that changes to the +/–3°F adjustment on the remote wall- mounted sensor have no effect, it is likely that an occupant used the keypad/display to make a Set Point Offset change. Cycle unit power to clear this situation and restore the ability to change the Set Point Offset from the +/–3°F adjustment on the remote wall-mounted sensor.

Remote Wall-Mounted Sensor with 55°F to 85°F

Adjustment (optional)

When the optional remote wall-mounted sensor with 55°F to 85°F adjustment dial is used, the UVC will effectively write the value of the set point dial to the Space Temp Set Point Input variable.

Note – If a network connection is using the Space Temp Set Point Input variable, do not use the optional remote wall-mounted sensor with 55°F to 85°F adjustment.

If it is intended that the LUI will be used by room occupants to adjust the Setpoint Offset, then you must not use the optional remote wall-mounted sensor with 55°F to 85°F adjustment. When using the optional remote wall-mounted sensor with 55°F to 85°F adjustment, the UVC will ignore any Setpoint Offset changes made at the LUI.

Effective Set Point Calculations

The UVC calculates the effective set point (Effective Set Point Output) based on several factors. These factors include the six occupancy set points for heating and cooling (Occupancy Temperature Set Point), occupancy mode, the value of the network variables Space Temp Set Point Input, Set Point Offset Input, and the Set Point Shift Input as well as the optional wall- mounted sensor’s set point adjustment knob. As always, network inputs have priority over hardwired connections.

The UVC determines if heating or cooling is required based on the current unit mode (Heat/ Cool Mode Output) and then calculates the required set point for heating or cooling. After calculating, the Effective Set Point Output network variable is set equal to the calculated set point. The Effective Set Point Output is the temperature set point that the UVC maintains, which normally appears on the keypad/display.

McQuay OM 751

27

Page 27
Image 27
American Standard UV05 manual Remote Wall-MountedSensor with +/-3F, Adjustment optional, Effective Set Point Calculations