UVC Configuration Parameters

Configuration Parameter Name

Abr.

Notes

Default

LUI Menu

Item1

 

 

 

 

Primary Cool Proportional Band

 

 

18°F (10°C)

 

 

 

 

 

 

Primary Cool Integral Time

 

 

180 sec

 

 

 

 

 

 

Secondary Cool Proportional Band

 

 

18°F (10°C)

 

 

 

 

 

 

Secondary Cool Integral Time

 

 

600 sec

 

 

 

 

 

 

Discharge Air Temp Proportional Band

 

 

4°F (2.22°C)

 

 

 

 

 

 

Discharge Air Temp Integral Time

 

 

300 sec

 

 

 

 

 

 

CO2 Proportional Band2

 

 

100 PPM

 

CO Integral Time2

 

 

600 sec

 

2

 

 

 

 

 

 

 

 

Ventilation Cooling Low Limit Setpoint

VCLL

discharge air low limit during ventilation or economizer cooling

54°F (12°C)

d2

 

 

 

 

 

Mechanical Cooling Low Limit Setpoint

MCLL

discharge air low limit during mechanical (compressor) cooling

45°F (7°C)

d3

 

 

 

 

 

Discharge Air High Limit

DAHL

 

140°F (60°C)

 

 

 

 

 

 

Space Fan Off Delay

 

 

30 sec

 

 

 

 

 

 

Fan Cycling Configuration

 

space fan operation during occupied, standby and bypass

2

CF

 

 

occupancy modes: 2 = continuous, 3 = cycle

 

 

 

 

Space Fan Speed Changes Per Hour

 

example: 6/60min = 10min (maximum of 1 fan speed change every

6

 

 

 

10min when fan in auto)

 

 

 

 

 

Space Fan Run Time Reset

 

reset total run time: 1 = reset (you must return the variable back to

0

 

 

 

0 after reset)

 

 

 

 

 

Compressor Run Time Reset

 

reset total run time: 1 = reset (you must return the variable back to

0

 

 

 

0 after reset)

 

 

 

 

 

Compressor Enable

 

0 = disable, 1 = enable

1

C!

 

 

 

 

 

Compressor Minimum On Time

 

 

180 sec

 

 

 

 

 

 

Compressor Minimum Off Time

 

 

300 sec

 

 

 

 

 

 

Compressor Cooling Lockout Setpoint

CCLO

OA temperature below which compressor cooling is not allowed

63.5°F (17.5°C)

 

 

 

 

 

 

Compressor Envelope Cool Max In

 

 

120°F (48.89°C)

 

 

 

 

 

 

Compressor Envelope Cool Min In

 

 

28°F (-2.22°C)

 

 

 

 

 

 

Compressor Envelope Cool Max Out

 

 

160°F (71.11°C)

 

 

 

 

 

 

Compressor Envelope Cool Min Out

 

 

40°F (4.44°C)

 

 

 

 

 

 

Compressor Envelope Cool Max Ratio

 

 

0.00

 

 

 

 

 

 

Compressor Envelope Cool Max Offset

 

 

88°F (48.89°C)

 

 

 

 

 

 

Compressor Envelope Cool Min Ratio

 

 

0.0

 

 

 

 

 

 

Compressor Envelope Cool Min Offset

 

 

-4°F (-2.22°C)

 

 

 

 

 

 

Auxiliary Heat Start Differential

AHSD

degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A1

 

 

 

 

 

Auxiliary Heat End Differential

AHED

degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A2

 

 

 

 

 

Auxiliary Heat Configuration

 

0 = normally open heat device (hot water valve, etc.),

0

A3

 

 

1 = normally closed heat device (electric heat, etc.)

 

 

 

 

Space Humidity Sensor Enable2

 

0 = disable, 1 = enable (this variable will be factory set to 1 when

0

 

 

 

the unit is ordered with optional humidity sensor)

 

 

 

 

 

Outdoor Humidity Sensor Enable2

 

0 = disable, 1 = enable (this variable will be factory set to 1 when

0

 

 

 

the unit is ordered with optional humidity sensor)

 

 

 

 

 

48

McQuay OM 751

Page 48
Image 48
American Standard UV05 manual UVC Configuration Parameters