TROUBLESHOOTING
PLEASE READ THIS SECTION BEFORE REFERENCING SPECIFIC DIAGNOSTIC MESSAGES.
1.Ensure the installation detail conforms with the recommendations contained in the Installation section of this manual.
2.Understanding the Principle of Operation is an asset when troubleshooting. A basic description
is provided in the section titled OPERATION. For a more detailed understanding please contact your NORTEC representative.
3.When contacting your local representative or NORTEC for troubleshooting assistance, please ensure the serial number has been obtained for reference purposes.
4.Whenever the troubleshooting steps indicate a problem with the main PCB, first check all connections at the main control board.
DIAGNOSTIC PROCEDURES - TROUBLESHOOTING
The RESDELUX controller provides a number of messages to simplify troubleshooting procedures. The following table presents fault messages displayed by the controller, their meaning and possible corrective actions. Refer to the following section for detailed information about terms used in the table.
Table #4 - Troubleshooting Guide
Unit Status Lamp | Symptom | Corrective actions |
| |
Yellow | Green |
| ||
|
|
| ||
On | On | Maximum water level | This usually happens on initial | |
|
| inside cylinder. | (normal). |
|
|
|
| Water is concentrated with minerals inside the cylinder. |
|
|
|
| Let unit run, yellow light will disappear when the unit is at full | |
|
|
| output. This may take a day or two. |
|
Off | Off | No power to the | Check for main power supply fault. |
|
|
| board. | Turn power switch to ‘Drain’ position. If drain valve is activated | |
|
|
| (sound of solenoid), check connection to the board or board itself. | |
|
|
| When no sound present, check fuse (replace with 1.5A if needed), | |
|
|
| transformer (voltage should be present between fuse holder and | |
|
|
| ground screw). |
|
1 flash | Off | Over current. | Check drain valve operation, drain time, possible drain | restrictions. |
sequence |
| Operating amperage | Check if fill valve leaks (not holding supply water). |
|
|
| exceeded 130% of | Back pressure may also cause very conductive water | conditions. |
|
| rated amps. Water is | ||
|
| Was the humidifier short cycling? |
| |
|
| drained from the |
| |
|
| Check for short cycling. |
| |
|
| cylinder (drain valve |
| |
|
|
|
| |
|
| on for 10 min.). |
|
|
2 flashes in | Off | No current | Check water level in the cylinder - should be more than ¼ full. If not | |
sequence |
| detection for 30 | check fill rate, 24 VAC voltage on fill valve terminals (unit must be | |
|
| minutes with | on with call for humidity - green light steady on). Verify fresh water | |
|
| continuous call for | supply to the humidifier. Leaking drain valve can be at fault | |
|
| humidity. | (minerals blocking the plunger). |
|
|
|
| If cylinder is more than ¼ full, check primary power, connections to | |
|
|
| the cylinder, continuity of wires to cylinder. |
|
|
|
| Are power wires connected to proper terminals on the cylinder? | |
|
|
| (Color coding) |
|
|
|
| Possibly wrong cylinder type. |
|
|
|
| Low water conductivity. |
|
4 flashes in | Off | End of cylinder life - | Check water level in the cylinder, should be about ¾ full. | |
sequence |
| change cylinder. | Check for foaming if water level lower or cylinder life shorter than | |
|
|
| expected. |
|
|
|
| Change cylinder, clean drain valve. |
|
|
|
|
|
|
- 11 -