(9)Control Panel installation for standard Octo hardware is explained in the under Control Panel section.

(10)The nozzles on the Octo units are pointed straight forward when shipped but these can be oriented in any direction that will not have the plume strike a solid object or another plume for at least 16 feet. Figure 9 AFE Octo Nozzle Spray Pattern helps in visualization of these AIRFOG plumes.

(11)The center vertical rail is to be mounted in the center of the duct and attached to the manifold rails using the supplied hardware. It is important that the center vertical rail is sized correctly and securely fastened to the top and bottom of the duct.

10-20

Page 26 2008-04-11

Page 33
Image 33
Nortec Industries Airfog Series installation manual 10-20