Nortec Industries NHTC Series installation manual 10-10, Page

Models: NHTC Series

1 44
Download 44 pages 54.78 Kb
Page 14
Image 14
Page 7 2008-02-18

Variable Name

R=Read

Description

LonWorks SNVT

W=Write

 

 

 

nvoFault_x

R

Indicates unit fault status.

SNVT_switch

0=no fault, 1=fault.

 

Binary Value

 

 

 

 

 

 

 

Indicates if a high-water level

 

nvoHWSensor_x

R

condition exists in the humidifier

 

 

Binary Value

cylinder.

 

 

 

0=normal, 1=high water condition

 

 

 

Reads configuration status for

 

 

 

network-enabled sensing or

 

 

 

control.

 

nvoNetSensor_x

R

0=%RH or %demand input is not

SNVT_switch

 

Binary Value

from the network

 

 

 

1=%RH or %demand input is from

 

 

 

the network

 

 

 

 

 

nvoDisable_x

R

Reads remote disable status.

SNVT_switch

0=humidifier enabled,

 

Binary Value

1=humidifier disabled by network

 

 

 

 

 

 

R

Indicates security loop status.

 

nvoSecurity_x

0=Sec. loop open,

SNVT_switch

 

Binary

1=Sec. loop closed

 

 

 

 

 

 

 

 

 

R

Reads service requirement status.

 

nvoService_x

0=no service required,

SNVT_switch

 

Binary Value

1=service required

 

 

 

 

 

 

 

 

nvoStatus_x

R

Reads humidifier status.

SNVT_switch

 

Binary Value

0=standby, 1=humidifying.

 

 

 

 

 

 

R

Indicates that the Nortec Links

 

nvoConnection_x

module is communicating with the

SNVT_switch

 

Binary Value

Humidifier

 

 

 

 

 

 

 

Writes remote disable status.

 

nviDisable_x

W

0=humidifier enabled,

SNVT_switch

 

Binary Value

1=humidifier disabled from

 

 

 

network

 

 

 

 

 

 

 

Writes configuration status for

 

 

 

network-enabled sensing or

 

 

W

control.

 

nviNetSensor _x

0=%RH or %demand input is not

SNVT_switch

 

Binary Value

from the network

 

 

 

1=%RH or %demand input is from

 

 

 

the network

 

 

 

 

 

10-10

Page 7 2008-02-18

Page 14
Image 14
Nortec Industries NHTC Series installation manual 10-10, Page