(1) NORTEC LINKS 2 START-UP CHECKLIST

WIRING

Humidifier-to-Humidifier Connection:

Each individual humidifier linked to lead unit.

Connection must be daisy-chained to other units.

BMS Network Connection:

Lead unit wired to BMS system (Twisted Pair or Ethernet).

Network activity verified.

Controls Wired:

Directly to humidifiers or through BMS network.

(2) START-UP PROCEDURE

ˆ

ˆ

ˆ

ˆ

ˆ

(1)Ensure power is being supplied to the humidifier, Nortec Links Module and Nortec OnLine module. For BACnet/IP adjust network IP settings. (If this information is provided, factory will perform necessary IP assignment).

(2)After power-up, verify network communication.

(3)Map desired network variables to BMS.

(4)Verify variable operation after mapping is complete.

(5)Perform regular humidifier start-up check.