Nortec Industries NHTC Series Variable Definitions, 10-10, Unit must be configured for dual, Page

Models: NHTC Series

1 44
Download 44 pages 54.78 Kb
Page 13
Image 13
Variable Definitions

 

Table 3.

Variable Definitions

 

 

 

 

 

Variable Name

R=Read

Description

LonWorks SNVT

 

W=Write

 

 

nvoHourOpt_x

R

Indicates the number of hours the

SNVT_count_inc

humidifier cylinder has been in

 

Analogue Value

operation.

 

 

 

 

 

 

 

Reads to capacity limitation

 

nvoCapLimit

R

applied to the unit output.

SNVT_switch

 

Analogue Value

(50-100%)

 

 

 

 

 

 

 

 

nvoRHDem1_x

R

Reads Ch.1 input signal in %RH

SNVT_switch

or demand to humidifier.

 

Analogue Value

(0-100%)

 

 

 

 

 

nvoSet1_x

R

Reads Ch.1 setpoint setting.

SNVT_switch

 

Analogue Value

(10-90%)

 

 

 

 

 

 

 

Reads Ch.2 input signal in %RH

 

 

 

or demand to humidifier.

 

nvoRHDem2_x

R

(0-100%)

SNVT_switch

 

Analogue Value

Unit must be configured for dual

 

 

 

 

 

 

channel operation.

 

 

 

 

 

 

 

Reads Ch.2 setpoint setting.

 

nvoSet2_x

R

(10-90%)

SNVT_switch

Unit must be configured for dual

 

Analogue Value

 

 

 

channel operation.

 

 

 

 

 

nvoSysDemand_x

R

Reads humidifier system

SNVT_switch

 

Analogue Value

demand. (0-100%)

 

 

 

 

 

nviCapLimit

R

Sets the humidifier’s unit

 

 

Analogue Value

capacity. (50-100%)

 

 

 

 

 

 

 

Writes Ch.1 demand or %RH

 

 

 

level. Allows BMS control of

 

nviRHDem1_x

W

humidifier output. (0-100%)

SNVT_switch

 

Analogue Value

Unit must be configured for

 

 

 

 

 

 

networked demand

 

 

 

 

 

 

 

Writes Ch.2 demand or %RH

 

 

 

level. Allows BMS control of

 

nviRHDem2_x

W

humidifier output. (0-100%)

SNVT_switch

 

Analogue Value

Unit must be configured for

 

 

 

 

 

 

networked demand

 

 

 

 

 

nviSet1_x

W

Writes Ch.1 setpoint (0-90%)

SNVT_switch

 

Analogue Value

 

 

nviSet2_x

W

Writes Ch.2 setpoint (0-90%)

SNVT_switch

 

Analogue Value

 

 

10-10

Page 6 2008-02-18
Page 13
Image 13
Nortec Industries NHTC Series Variable Definitions, 10-10, Unit must be configured for dual, channel operation, Page