| Table 3. | Variable Definitions |
| |
|
|
|
| |
Variable Name | R=Read | Description | LonWorks SNVT | |
| W=Write |
|
| |
nvoHourOpt_x | R | Indicates the number of hours the | SNVT_count_inc | |
humidifier cylinder has been in | ||||
| Analogue Value | operation. |
| |
|
|
|
| |
|
| Reads to capacity limitation |
| |
nvoCapLimit | R | applied to the unit output. | SNVT_switch | |
| Analogue Value |
| ||
|
|
| ||
|
|
|
| |
nvoRHDem1_x | R | Reads Ch.1 input signal in %RH | SNVT_switch | |
or demand to humidifier. | ||||
| Analogue Value |
| ||
|
|
|
| |
nvoSet1_x | R | Reads Ch.1 setpoint setting. | SNVT_switch | |
| Analogue Value |
| ||
|
|
|
| |
|
| Reads Ch.2 input signal in %RH |
| |
|
| or demand to humidifier. |
| |
nvoRHDem2_x | R | SNVT_switch | ||
| Analogue Value | Unit must be configured for dual |
| |
|
|
| ||
|
| channel operation. |
| |
|
|
|
| |
|
| Reads Ch.2 setpoint setting. |
| |
nvoSet2_x | R | SNVT_switch | ||
Unit must be configured for dual | ||||
| Analogue Value |
| ||
|
| channel operation. |
| |
|
|
|
| |
nvoSysDemand_x | R | Reads humidifier system | SNVT_switch | |
| Analogue Value | demand. |
| |
|
|
|
| |
nviCapLimit | R | Sets the humidifier’s unit |
| |
| Analogue Value | capacity. |
| |
|
|
|
| |
|
| Writes Ch.1 demand or %RH |
| |
|
| level. Allows BMS control of |
| |
nviRHDem1_x | W | humidifier output. | SNVT_switch | |
| Analogue Value | Unit must be configured for |
| |
|
|
| ||
|
| networked demand |
| |
|
|
|
| |
|
| Writes Ch.2 demand or %RH |
| |
|
| level. Allows BMS control of |
| |
nviRHDem2_x | W | humidifier output. | SNVT_switch | |
| Analogue Value | Unit must be configured for |
| |
|
|
| ||
|
| networked demand |
| |
|
|
|
| |
nviSet1_x | W | Writes Ch.1 setpoint | SNVT_switch | |
| Analogue Value |
|
| |
nviSet2_x | W | Writes Ch.2 setpoint | SNVT_switch | |
| Analogue Value |
|
|