Configuration Variables nviInputType_x = 1 nviNetSensor_x = 1
Control Variables
nviSet1_x = Room Setpoint
nviRHDem2_x =
= 0 Unit Enabled
Readable Variables nvoStatus_x = 1 Humidifying
=0 Standby
nvoService_x = 1 Service Required
=0 No Service Required nvoFault_x = 1 Fault
=0 No Fault
nvoSysDemand_x = System
nvoDisable_x = 1 Unit Disabled = 0 Unit Enabled
NHTC
Figure 1. Sample Humidification Applications
Room-Sensed %RH Feedback with Duct Hi-Limit Sensing
Configuration Variables nviInputType_x = 0 nviNetSensor_x = 1
Control Variables
nviSet1_x = Room Setpoint
nviDisable_x = 1 Unit Disabled = 0 Unit Enabled
Readable Variables nvoStatus_x = 1 Humidifying
=0 Standby
nvoService_x = 1 Service Required
=0 No Service Required nvoFault_x = 1 Fault
=0 No Fault
nvoSysDemand_x = System
nvoDisable_x = 1 Unit Disabled = 0 Unit Enabled
NHTC
Figure 2. Sample Humidification Applications
Control Feedback (0-100%) with Duct Hi-Limit Sensing